2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on PC board is broken please change it with the type of T 3.15A /250VAC.
4. The wiring method should be in line with the local wiring standard.
5. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no
less than 3mm. Such means for disconnection must be incorporation in the fixed wiring.
6. The installation height of the indoor unit is recommended from 2.5m to 2.7m.
7.
The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m. If exceeded, the
diameter of the wire should be enlarged according to the local wiring standard.
8. The waste battery shall be disposed properly.
9.we can get the 4 different ESP through adjust the indoor unit
PCB SW1-4 and SW1-5, please refer below:
1. Applicable ambient temperature range:
The machine is adaptive in following situation
Drain pan
Safety Precautions
Parts and Functions
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
32/23 C
18/14 C
46/24 C
18 C
27 C
15 C
24/18 C
-15 C
Evaporator
Air outlet frame
Electrical components
Case
Drain pan
AD25S2SS1FA
AD35S2SS1FA
AD50S2SS1FA
AD71S2SS1FA
AD25S2SS2FA
AD35S2SS2FA
AD50S2SS2FA
AD71S2SS2FA
SW01
[1]
[2] [3] [4] [5] [6] [7] [8]
-- -- -- 0 0 -- -- --
-- -- -- 0 1 -- -- --
-- -- -- 1 0 -- -- --
-- -- -- 1 1 -- -- --
0Pa
10Pa
20Pa
30Pa
Static pressure
The pump drain opening
Attention: cut off the power supply to adjust the SW1-4, and SW1-5, or else the operation is invalid.