Functions and control 
15 
Domestic air conditioner 
7 Functions and control
7.1 Main functions and control specification
7.1.1 Automatic operation 
 When the running mode is turned to automation after starting the system, the system will first determine 
the running mode according to the current room temperature and then will run according to the determined mode. 
Tr in the following selection conditions means room temperature, Ts means setting temperature, Tp means 
temperature of indoor coil pipe    
 TrıTs-3ć      Choose Cooling Mode 
Tr˘Ts-3ć     Choose Heating Mode 
   After turning to the automation mode, the running mode can be switched between cooling mode, fan mode 
and heating mode according to the change of the indoor ambient temperature. But the automatic conversion 
between cooling mode and heating mode must be conducted after 15 minutes. 
7.1.2 Cooling operation mode 
 Temperature control range:  16ć---30ć 
 Temperature difference:     r1ć 
* Control features: When Tr˄input airflow˅>Ts˄set temperature˅+ temperature Backlash A, the
compressor will be opened, the indoor fan will operate at the set speed and the mode signal will be sent to the 
outdoor system. When Tr
˄input airflow˅ Ts˄set temperature˅ temperature Backlash B, the compressor will 
be shutted, the indoor fan will operate at the set speed and the mode signal will be sent to the outdoor system. The 
system will keep the original status if Tr= Ts.
Airflow speed control: (temperature difference 1ć)
Automatic: When TrTs+3ć, high speed.
When Ts+1ćTr<Ts+3ć, medium speed 
When Tr<Ts+1ć, low speed 
When the sensor is off, low speed 
When the airflow speed has no delay from the high to low switching, the speed should be delayed for 3 minutes 
(remain at high speed for 3 minutes.) before the next switch. 
Manus: When the system is operating, you can set the high, medium or low speed manually. (When the sensor is 
on or off, the system will change the speed 2 seconds after receiving the signal.) 
*Airgate location control: the location for the airgate can be set according to your needs.
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or
dehumidifying). When the compressor works continuously for 6 minutes and the temperature of the indoor coils
has been below one centigrade for 10 seconds, the compressor will be stopped and the malfunction will be
recorded in the malfunction list. The indoor system will continue to run. When the temperature of the indoor coil is
raised to 9ć, the compressor will be restarted again (the requirement of 3 minutes’ delay should be satisfied.)
*timing system on/off function.
*Dormant control function.