Installations
                                                                                                           
Domestic air conditioner
37
Led1  light
NO
YES
 Remove fan motor after 
switch off the power and restart
 the a/c ,the led 1 becomes light 
or  flash.
Fan motor is 
damaged,replace it 
with a new one.
YES
NO
YES
 
  Test the  fan motor terminal resistance 
between pin 310V and 0V,or pin15V and 0V 
of CN22 are close to 0mΩ with a multimeter 
after switch off the power .
NO
Remove the connection cable 
between CN23 of outdoor pcb and 
CN10 of module pcb,The led1 
becomes light or  flash.
YES
YES
The module pcb is 
damaged, replace it 
with a new one.
The outdoor pcb is 
damaged, replace it 
with a new one.
NO
            Measure the voltage 
       Between 3 and 4 of IC9 on the 
Outdoor mainboard with a Multimete .
 The voltage is a constant value of 0V 
                    DC to 5V DC
The outdoor pcb is 
damaged, replace 
it with a new one.
YES
NO
The outdoor pcb is 
well,and then check 
the cable
        If the voltage is a constant value 
         of 0V DC to 5V DC.Or  the voltage         
between Communication line(red ) and N(white    
line) is not  close to18V
         DC when only indoor charged.
YES
The indoor mainboard is 
damaged; replace it with a 
new one.
NO
 
       Test the outdoor power is
    supply 230VAC with a            
    multimeter when indoor and 
           outdoor are charged.
 
   LED2 light of  the outdoor 
NO
The module pcb  
is damaged, 
replace it with a 
new one.
NO
YES
Check the cable 
between outdoor 
and power 
(A)