36
SW01 SW02 Digital tube display
1
0 Td discharging temperature (unit:
℃)
1 Ta outdoor ambient temperature (unit:
℃)
2 Ts suction temperature (unit:
℃)
3 Te defrosting temperature (unit:
℃)
4 Toil oil temperature (unit:
℃)
5 Pd high pressure (unit: kg, one decimal)
6 Ps low pressure (unit: kg, one decimal)
7
Outdoor PMV valve open angle (unit: pls, max. display: 999)
(Press start for 5s to enter forced mode, all the indoor units' PMV are full open, ashing
display "480" and press stop for 5s to quit and display outdoor PMV valve open angle)
8
Valve state
The rst position: 4WV (0-OFF; 1-ON)
The second position: SV1 (0-OFF; 1-ON)
The third position: SV2 (0-OFF; 1-ON)
9
The rst position: high pressure switch (0-OFF; 1-ON)
The second position: low pressure switch (0-OFF; 1-ON)
The third position: heater (0-OFF; 1-ON)
A Tn module temperature (unit:
℃)
B Compressor current (unit: A, one decimal)
C Te defrosting temperature (unit:
℃)
D DC voltage of module (unit: V
E
Outdoor CT current (unit: A, one decimal)
Forced cooling alternate display ”CCC”, (Press start for 5s, all the indoor units are in cooling
state, and press stop for 5s to quit)
F
Forced heating (Press start for 5s, all the indoor units are in heating state, and press stop for
5s to quit) display “ HHH”, otherwise “---”
2 0-F If the communication is normal display indoor program version (one decimal) ,otherwise “---”
3 0-F Indoor type (0,4,5,6,7 ordinary indoor unit; 1-high wall; 2-fresh air; 3-heat recovery)
4 0-F Display indoor failure code, if no failure display “---”
5 0-F Indoor horse power (one decimal)
6 0-F
The rst and second position: indoor unit current operation mode (00-OFF, 01-Fan,
02-Cooling, 03-Dehumidify, 04-Heating)
The third position: outdoor unit capacity demand (0-no ; 1-yes)
7 0-F Indoor PMV valve open angle (unit: pls, max. display: 999)
8 0-F
Indoor unit
The rst position: oat switch (0-OFF; 1-ON)
The second position: pump (0-OFF; 1-ON)
The third position: heater (0-OFF; 1-ON)
9 0-F Indoor Ta ambient temperature (unit:
℃)
A 0-F Indoor TC1 gas temperature (unit:
℃)
B 0-F Indoor TC2 liquid temperature (unit:
℃)
C 0-F Indoor units: fan speed of indoor units(0-OFF, 1-Low, 2-med, 3-high)
E 0-F
Forced cooling (press "start" for 5s for cooling operation of indoor units and press "stop" for
5s to quit) display ”CCC”, otherwise “---“
F 0-F
Forced heating (press "start" for 5s for heating operation of indoor units and press "stop" for
5s to quit) display ”HHH”, otherwise “---“