27
Failure code
Failure code
display on
the outdoor
digital display
board
Failure code
denition
Failure code denition Remarks
59
Tliqsc temp. sensor
failure
Continuous disconnect for 60 seconds or
short circuit, failure alarm.
Resumable
64 CT value too high
When the CT current exceeds the specied
value for 5 consecutive seconds, failure
alarm. The failure will be removed after 3
minutes. Failure is locked if it occurs 3 times
in one hour.
Once failure
locked, un-
resumable.
71-0 DC Fan1 failure
The failure will alarm when it runs below
20 rpm for 40 seconds or below 20% of the
target value for 2 minutes.
The failure will be removed after 3 minutes.
Failure is locked if it occurs 3 times in one
hour.
Once failure
locked, un-
resumable.
71-1 DC Fan2 failure
78 Lack of refrigerant
1.Cooling: Ps≤0.2MPa for 30 consecutive
minutes, failure alarm. Ps≥0.3MPa for 30
consecutive minutes, failure removed.
2.Heating:Both LEVa equals to 470pls and
Ts-Ps≥20
℃
for 60 consecutive minutes,
failure alarm. Ps≥0.2MPa for 30 consecutive
minutes, failure removed.
Resumable
81
Inverter temp. too
high
Inverter temp.≥90
℃
, failure alarm. Inverter
temp. ≤70
℃
, failure removed. Failure is
locked if it occurs 3 times in one hour.
Once failure
locked, un-
resumable.
82
Compressor current
protection
When the compressor current exceeds the
specied value for 5 consecutive seconds,
failure alarm. The failure will be removed
after 3 minutes. Failure is locked if it occurs 3
times in one hour.
Once failure
locked, un-
resumable.
83 Model setting error
Model setting does not match the outdoor
unit.
Once failure
locked, un-
resumable.
110
The inverter module
over current
(hardware)
Module hardware over current. Failure is
locked if it occurs 3 times in one hour.
Once failure
locked, un-
resumable.
Instantaneous over current of hardware at
rectier side of inverter module. Failure is
locked if it occurs 3 times in one hour.