EasyManua.ls Logo

Haier CA0035EAND - Technical Parameters; Performance Parameters

Haier CA0035EAND
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
Technical Parameters
Performance Parameters
Model
Item
CA0035EAND
CA0070EAND
CA0130EAND
Cooling capacity kW
30
65
13
0
Heating capacity kW
33
70
13
5
Cooling rated power input kW
9.4
19
.2
38
.4
Heating rated power input kW
9.6
19
.1
38
.2
Max. power input kW
16.3 28
56
Max. running current A
27.5
55
11
0
Compressor
Type -- Flexible scroll compressor
Qty. EA
1
2
4
Rated power kW
18
Capacity regulating range
--
-
100%
50%,100%
25
%,50%,
75%,100%
Refrigerant
Type ---
R410a
Charge kg
5.5
6X2
5.8X4
Refrigerant throttling device ---
Electronic expansion valve
Power supply ---
3N~, 380V, 50Hz
Air-side
heat
exchanger
Type ---
Slit
fin
+
efficient inner grooved copper tube
Fan type ---
Axial flow fan
Fan power kW
0.7
1.5
3
Qty. EA
1
2
4
Water-side
hea
t
exchanger
Type
---
Plate heat
exchanger
Shell tube heat exchanger
Flow m
3
/h
5.6
12
24
Water pressure
loss
kPa
40
45 60
Connection
dimension
--
-
DN65
2’’
2 1/2’’
Scaling factor
m
2
·°C/kW
0.018
Standard
pressure-bearing
Kpa
1000
Net
dimensions
Len
gth X Width X
Height
mm
918X1038
X1810
2060X780
X2170
2060X1603
X2170
Weight
Net weight kg
270
630
1090
Operating weight kg
300
670
1200
Safety
protection
Hi
gh/low pressure protection, water-break delay protection, anti-freezing protection, motor
overload, overheating protection, phase failure and phase sequence protection.
Note:
1. Nominal refrigerating condition: water outlet temperature is 7, ambient temperature is 35, and
water flow is 0.172[m
3
/(h·kW)].
2. Nominal heating condition: water outlet temperature is 45, ambient temperature is 7 for dry bulb
and
6 for wet bulb, and water flow is listed in the above table.
3. Unit operating range: conforming to GB/T 18430.1& GB/T 18430.2.
4. Scaling factor of circulating water: 0.018m
2
·℃/kW.
5. The specifications in the table may vary with changes in product design without prior notice.
9
36
CA0100EAND
98
103
28.9
28.7
45.6
82.5
3
27
33%,67%,
100%
5.8X3
2
4
18
50
2’’
2060X1603
X2170
970
102
0

Other manuals for Haier CA0035EAND