Commercial Air Conditioner Model: HBU-18CF03
HDU-42CF03/H HPU-42HF03
21
If after over 2 hours vacuumizing, the vacuum degree is below -755mmHg, close the V
L and
V
H on the
meter separator and stop vacuumizing. 1 hour later to confirm if the vacuum degree changes. If changes,
it indicates there is leaking point in the system. Check the leaking point and
repair.
After finishing the above vacuumizing, change the vacuum pump into refrigerant pump to charge the
refrigerant.
When the total length (L) of the two indoor units' connecting pipe is less than 5m, it is unnecessary to
charge additional refrigerant.
If the connecting pipe (L) exceeds 5m, it shall charge Mg additional refrigerant per meter.
That is: Refrigerant charging amount = (L-5) x M (g)
For the unit with liquid pipe 6.35mm, M=30
For the unit with liquid pipe 9.52mm, M=65
Only in COOLING operation can charge the additional refrigerant.
When charging, the refrigerant shall be charged from the charging nozzle of low pressure vavle.
Be carefull when charging refrigerant, do not let the air mix into the system,and must charge the additional
refrigerant in liquid condition.
Charging amount of refrigerant
Electric wiring
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER
SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS.
GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING
LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round
type crimped terminal lugs with insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m
length wires with less than 2% voltage drop.)
WARNING
30mA
Item
Model
Phase
1
Switch breaker
(A)
Circuit breaker
Overcurrent protector
rated capacity (A)
Power source
wire size
(minimum)
30 20 2.5mm
2
3
30 20 2.5mm
2
Switch
breaker
Earth leakage breaker
Leak
current
30 30mA
30
HDU-42CF03/H
HBU-18CF03