Commercial Air Conditioner       Model: HBU-18CF03 
       HDU-42CF03/H HPU-42HF03 
 
71 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
10.2 Failure code 
The remote receiver, wired controller and indoor PCB indicator all can indicate the failure code. 
10.2.1 Failure code list 
Power lamp flash 
times/LED on PCB 
flash times 
failure description  reasons  treatment 
1 Indoor ambient temp. 
sensor failure 
sensor broken down or short 
circuit for more than 2m 
continuously
 
due to the 
signal,resumable  
2 Indoor pipe temp. 
sensor failure 
sensor broken down or short 
circuit for more than 2m 
continuously
 
due to the 
signal,resumable
 
4  Outdoor pipe temp. 
sensor failure 
sensor broken down or short 
circuit for more than 2m 
continuously
 
due to the 
signal,resumable
 
8 Communication failure 
between panel and 
indoor unit 
communication abnormal for 
more than 4m continuously
 
due to the 
signal,resumable
 
16 Low pressure 
malfunction 
low pressure switch acts for 
30m
 
Need to be checked, 
reset 
10.2.2 Sensor malfunction 
If indoor ambient temp. sensor and indoor pipe temp. sensor are valid, there is no outdoor sensor, in 
the following conditions, the unit will confirm the sensor is failure:   
Mainboard checks that the sensor is in open circuit, short circuit or close to short circuit continuously 
for 2 minutes, the mainboard will confirm that sensor is failure, the system will stop running, alarm 
occurs; If the signal is resumed, the system will resume automatically.   
If indoor ambient temp. sensor and indoor pipe temp. sensor is valid, also there is outdoor sensor, in 
the following conditions, the unit will confirm the sensor is failure:   
Mainboard checks that the outdoor pipe temp. sensor is in open circuit, short circuit or close to short 
circuit continuously for 2 minutes, the mainboard will confirm that sensor is failure, the system will 
stop running, alarm occurs; If the signal is resumed, the system will resume automatically.