Installer settings
- To open the installer settings, press switch off the system, then press and
at the same time for 10 seconds.
- When menu is open, press or to change the value of the settings.
- Press to confirm the settings.
- Press to close the menu.
Parameters
, ,
,
Description
Off-peak signal type
Off-peak logic type
When you use off-peak time clock control, first determine
the type of signals,Only allow professional installers to operate.
- In two ways using heat pump,should set in the installer
settings
-01 manually set off-peak time;
-02 switch signals by power companies.
NO
01
ON
1 1,2,3
1
8h 5-10h
1,2,3
NO , NC
01 , 02
ON , OF
NO
NO , NC
Fan speed
- 1 corresponds to water heaters without ducts.
- 2 corresponds to semi-ducting, with a single duct installed.
- 3 corresponds to ducts on both the inlet and the outlet.
Heat pump working time
- If heat pump work more than Set Time, start electric heating.
Auxiliary Heating
- 1 corresponds to electrical back-up.
- 2 corresponds to electrical and boiler back-up.
- 3 corresponds to electrical and solar back-up.
Boiler output signal type
,
,
, ,
-
Factory
setting
Adjustment
range
Avoid Legionella
- This parameter is used to activate the legionella protection
mode.
- Once every 7 days, all domestic hot water is heated to 65�.
- NO corresponds to boiler Normally Open Signal.
- NC corresponds to boiler Normally Close Signal.
- NO corresponds to Normally Open Signal.
- NC corresponds to Normally Close Signal.
,