Display 
temperature 
value 
Display current 
temperature value of 
each sensor 
Short circuit or 
disconnection of 
RT-SNR 
Control  according  to  the 
environmental  temperature  scope  of 
23℃≤RT<28℃ 
Short circuit or 
disconnection of 
R-SNR 
Defrost after 30 minutes, the fan and the 
air switch continuous operation, after that 
the PC air switch go into 10 minutes off 
the 10 minute cycle 
Short circuit or 
disconnection of 
F-SNR 
Compressor  enters  the  circulation 
state  under  which  it  opens  for  15 
minutes  and  then  closes  for  15 
minutes every 30 minutes 
Short circuit or 
disconnection of 
S-SNR 
PC air switch go into 10 minutes off the 
20 minute cycle 
Short circuit or 
disconnection of 
D-SNR 
Automatic  defrosting  procedure  is 
carried  out  normally,  and  the 
defrosting time is 30 minutes. 
Display board and 
power board can not 
be connected for 2 
minutes 
Temperature of 
defrosting sensor can 
not reach 12 degrees 
in 90 minutes after 
rising 
Short circuit or 
disconnection of 
D-SNR 
according to humidity 80% control 
 
【2】T mode 
Entering mode: Click the TEST button (or open the door, locked, press the "Fridge" 
button, press the "My zone" button on the 5). 
Exit mode: Under the condition of T4 click the TEST button (or T4, open the door, locked, press "Lock"