7.2.2 
Indoor fan motor malfunction
 
 
 
Indoor Display   
E14
 
 
 
Method of 
The rotation speed detected by the Hall IC during fan motor operation is used to determine   
Malfunction      
abnormal fan motor operation
 
Detection 
Malfunction     
when the detected rotation feedback singal don’t receiced in 2 minutes
 
Decision     
Conditions 
Supposed  Causes ■   
Operation halt due to breaking of wire inside the fan motor . 
■ 
  Operation halt due to breaking of the fan motor lead wires 
■ 
  Detection error due to faulty indoor unit PCB         
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Yes 
 
 
 
 
   
 
 
 
Yes 
 
YES 
NO 
whether terminal CON12 
and CN7 on indoor PCB 
well inserted or not?
Pull out and reinsert the terminals 
Electrify the machine again and turn it on in the cooling operation, 
Measure
  voltage between the  positions 1 ( red wire) and 
3(
 black wire) of Terminal CON12 on the indoor PCB 
NO 
the indoor pcb is damaged and need replace 
the voltage is about 
90-200vac  
 
check whether motor can 
run when turn on 
th
e unit 
the indoor motor is damaged and need 
replace
 
NO 
When motor is running Measure 
whether there is voltage pulse(0-5VDC) 
between the 
positions 2 (middle wire) 
and 3(
 black wire) of Terminal CN7 on 
the indoor PCB
 
the indoor motor is damaged and need 
replace
 
the indoor pcb is damaged and need replace 
NO 
YES 
HSU-18,22HVA103/R2(DB)   Service Diagnosis 
78
            Domestic Air Conditioner