7.2.9 High work-intense protection 
 
Indoor display    
 
 
 
E9
 
 
 
 
Method of 
High work-intense control is activated in the heating mode if the temperature being sensed 
Malfunction      
by the heat exchanger thermistor exceeds the limit. 
Detection 
 
Malfunction     
  Activated when the temperature being sensed by the heat exchanger thermistor rises above 
Decision         74
℃ twices in 30 minutes.
 
Conditions        
 
Supposed         ■  
Faulty electronic expansion valve 
Causes           ■  
Dirty heat exchanger 
■ 
Faulty heat-exchange sensor   
■ 
Insufficient gas 
 
Troubleshooting    
* Caution  
Be sure to turn off power switch before connect or disconnect connector,      or 
else parts damage may be occurred. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
YES 
NO 
the malfunction is reported 
after the machine has run 
for some time? 
Check room temperature and pipe 
temperature sensor. 
Electrify the machine again and turn it on with the remote 
controller, check whether the wind temperature is below 
74℃ 
YES 
NO 
the indoor unit blows poorly 
due to blocked filters or poor 
condition of the fan?
1) Clean the filters 
2) Reinstall the fan. 
Use some tools to measure the pressure of system 
The system is over charged with gas 
YES 
HSU-18,22HVA103/R2(DB)   Service Diagnosis 