10.4.9 Overheat Protection For Discharge Temperature
Outdoor display: LED1 flash 8 times
Method of
The Discharge temperature control is checked with the temperature being detected
Malfunction
by the Discharge pipe thermistor
Detection
Malfunction
when the compressor discharge temperature is above 116
Decision
Conditions
Supposed
Electronic expansion valve defective
Causes
Faulty thermistor
Faulty PCB
Troubleshooting
* Caution
Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify the machine again and turn it on with the remote controller,
then measure the temperature at the exhaust temperature sensor of
the compressor on the outdoor unit
The temperature exceeds
116
shortly after the
machine starts u
p
?
1) The cryogen may have been leaked during
installation, or there may be leakage in the piping
system.
2) There may be other causes to make the exhaust
temperature too high.
Malfunctions occur after running for some time even
though the measured temperature is below 116
. Pull
out the exhaust sensor and measure its resistance at
standard temperatures according to the
resistance-temperature table
The results deviate
much?
The sensor is damaged. Replace the sensor
with a new one.
The outdoor mainboard is damaged and needs be
re
p
laced
YES
NO
NO
YES
Service diagnosis
Domestic air conditioner
44

Other manuals for Haier J Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier J Series and is the answer not in the manual?

Haier J Series Specifications

General IconGeneral
BrandHaier
ModelJ Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals