EasyManua.ls Logo

Haier MRV 5-RC AD162MJERA - User Manual

Haier MRV 5-RC AD162MJERA
243 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
MRV 5-RC Service Manual
SYJS-03-2019REV.A
Edition: 2019-03

Questions and Answers

  • M
    Maria McdonaldSep 16, 2025
    How to fix current detecting circuit abnormal of compressor module in Haier MRV 5-RC AD162MJERA?
    • K
      Karen NguyenSep 16, 2025
      If the current detecting circuit of the compressor module is abnormal in your Haier Heat Pump, replace the inverter control board with abnormal current detection loop.
  • E
    Ernest ReillyAug 25, 2025
    What to do if four-way valve reversing failure in Haier Heat Pump?
    • J
      jordanalexanderAug 25, 2025
      In case of a four-way valve reversing failure in your Haier Heat Pump, the suggested solution is to have it correctly replaced by after-sales service on site and ensure the refrigerant is sufficient.
  • M
    martinezjeffreyAug 26, 2025
    How to fix outdoor compressor discharging temperature (Td1, Td2) too high failure in Haier MRV 5-RC AD162MJERA?
    • M
      Margaret SantosAug 26, 2025
      If the outdoor compressor discharging temperature (Td1, Td2) is too high in your Haier Heat Pump, the suggested solution is to have the discharging temperature sensor replaced by after-sales personnel on site.
  • L
    Laura MontgomeryAug 26, 2025
    What to do for fan motor module hardware over current in Haier MRV 5-RC AD162MJERA?
    • A
      Allison ParkerAug 27, 2025
      If the fan motor module in your Haier Heat Pump experiences a hardware over current issue, the solution is to replace the fan motor.
  • L
    loganbenitezSep 18, 2025
    What to do if radiator temp. sensor of compressor module is abnormal in Haier MRV 5-RC AD162MJERA Heat Pump?
    • M
      michaelariasSep 18, 2025
      If the radiator temperature sensor of the compressor module is abnormal in your Haier Heat Pump, replace the variable frequency board.
  • J
    Joseph DavisSep 23, 2025
    How to resolve AT24C04 EEPROM communication failure in Haier MRV 5-RC AD162MJERA Heat Pump?
    • S
      Sharon FergusonSep 23, 2025
      To resolve AT24C04 EEPROM communication failure, AT24C04 EEPROM data check failure, or IM EEPROM data or communication failure in your Haier Heat Pump, replace EE.
  • A
    angela59Sep 8, 2025
    How to fix emergency stop function switch failure in Haier Heat Pump?
    • J
      Joyce RoblesSep 9, 2025
      If the emergency stop function switch fails in your Haier Heat Pump, short circuit the CN18.
  • D
    Donald ClarkSep 9, 2025
    What to do if incorrect settings of quantity, address or capacity for outdoor unit in Haier MRV 5-RC AD162MJERA?
    • J
      Joseph WheelerSep 9, 2025
      If there are incorrect settings of quantity, address, or capacity for the outdoor unit of your Haier Heat Pump, the suggested solution is to research and lock the outdoor unit.
  • L
    Lisa WalkerSep 3, 2025
    What to do if discharging temperature sensor Td1 and Td2 failure in Haier MRV 5-RC AD162MJERA?
    • J
      John AndersonSep 3, 2025
      If the discharging temperature sensors Td1 and Td2 fail in your Haier Heat Pump, the solution is to have them correctly replaced by after-sales personnel on site.
  • M
    Matthew CrawfordSep 1, 2025
    What to do if outdoor unit compressor discharging temperature (Td1, Td2) too low failure in Haier MRV 5-RC AD162MJERA Heat Pump?
    • V
      vparrishSep 1, 2025
      If the outdoor unit compressor discharging temperature (Td1, Td2) is too low in your Haier Heat Pump, the suggested solution is to have the discharging temperature sensor replaced by after-sales personnel on site.

Summary

2. Specification

3. Dimension

5. Piping diagram

3. Control function

9. Noise level

10. Installation

10.1. Safety

Continues safety precautions, covering earthing, installation location, and handling of specific tools and refrigerants.

10.2. Installation instruction

Details installation place selection criteria to ensure proper ventilation, stability, and avoid environmental interference.

Outline and installation dimensions

Combination installation dimensions

10.3. Installation procedure

A. Refrigerant pipe connection

Continues refrigerant pipe connection instructions, covering valve welding and pipe cutting.

Cautions in piping installation

Provides cautions for piping installation, such as nitrogen charging during welding and cleaning pipes.

Pipe specification

2. Applicable range

Long pipe and high drop

Outdoor pipe dimension

Branch pipe selection:

Pipe installation

B. Leakage test

C. Evacuation

D. Check valve operation

E. Additional refrigerant charging

Pipe insulation

10.4. Electric wiring and the application

Outdoor unit leakage protection switch and circuit breaker

Provides specifications for leakage protection switches and circuit breakers for outdoor units, including current ratings and wire sizes.

Power line installation instructions

Communication wiring figure (Wired)

Communication wiring figure (wireless)

11. Branch pipe dimension

3-pipe system

Details branch pipe dimensions for 3-pipe systems, showing diagrams and size specifications for manifold pipes.

2-pipe system

Model FQG-B1350 A

Model FQG-B2040 A

12. Gather pipe dimension

Manifold pipe

Model HZG-R40 B

Model HZG-R40 B (Continuation)

2. Dimension

3. Piping diagram

All cooling

Illustrates piping diagrams for different operating modes: All cooling and Cooling > Heating.

Cooling Heating

Illustrates piping diagrams for different operating modes: Cooling > Heating.

All heating; Heating Cooling;

Heating standby

Illustrates piping diagrams for All heating / Heating > Cooling and Heating standby modes.

Cooling OFF

Illustrates piping diagrams for Cooling OFF mode.

4. Wiring diagram

5. Installation

Warning

Attention

Prohibitions

Do not install at such places

Combinations

(1) Inspection items after installation

Lists critical inspection items after installation, covering security, leakage, insulation, and wiring.

1. Pre-installation

2. Preparation before installation

3. Installation of valve box

4. Refrigerant pipe Installation

Attention item for piping connection

Highlights critical points for piping connection, including tool usage and torque.

Selection of piping dimensions

Connection example 1: Connect an indoor unit to the downstream of the valve box

Illustrates connecting an indoor unit to the downstream of a valve box.

Connection example 2: with branching in the downstream of the valve box

Illustrates connecting with branching in the downstream of the valve box.

<Table 5> Total capacity and pipe dimensions (mm) of the indoor units

Pipe connection

Note:

Provides notes on pipe connection, emphasizing confirmation of HP/suction gas pipes and connection to the valve box.

(2) Inspection upon delivery

(1) Inspection items after installation

If the installation of valve box is secure?

Checks if the valve box installation is secure, looking for falling off, vibration, or noise.

If gas leakage inspection is completed?

Verifies if gas leakage inspection has been completed, checking for no heating/cooling issues.

If complete insulation is achieved (refrigerant piping and tubing connections)?

Checks if complete insulation is achieved for refrigerant piping and tubing connections, looking for water leakage.

If the voltage of the power supply is consistent with that on the nameplate?

Verifies if the power supply voltage matches the nameplate, checking for out of service or burnt conditions.

If there is improper wiring or piping?

Checks for improper wiring or piping, looking for out of service or burnt conditions.

If there is construction without grounding?

Checks for construction without grounding, identifying danger in electric leakage.

If the thickness of the wire is as specified?

Verifies if the wire thickness is as specified, checking for out of service or burnt conditions.

<Notes>

Please do not let any type of gas other than the specified refrigerant go into the refrigeration system;

Prohibits using gases other than the specified refrigerant in the system.

In case of refrigerant leakage during operation, please replace the gas. (Fill the refrigerant at the outdoor unit)

Instructs to replace refrigerant if leakage occurs during operation, filling it at the outdoor unit.

Select piping material

Attention item for piping connection

To connect a pipe to or remove it from the valve box, do use pliers for screws and torque spanner;

Instructs to use pliers and torque spanner for connecting/removing pipes from the valve box.

<Note>

If no torque wrench is available, act as the follows.

After the work, make sure there is no air leakage.

<Note>

For pipe welding, do not use antioxidant, for its residue may cause tube blocking and component fault.

Warns against using antioxidant for pipe welding to prevent tube blocking.

<Table 1> Total capacity and pipe dimensions (mm) of the indoor units

<Table 3> Dimensions (mm) of connection pipe of the vale box

Pipe connection

Provides notes on pipe connection, emphasizing confirmation of HP/suction gas pipes and connection to the valve box.

Note 1:

1. Outdoor PCB photo and dip switch setting

Outdoor dip switch introduction

Identification:

Explains the identification of physical and functional master/slave units and the purpose of dip switches.

BM1 introduction

Details the functions of BM1 dip switches for outdoor unit settings like searching, mode, static pressure, and valve box type.

BM2 introduction

BM2_1

Details BM2 dip switches for outdoor unit heat mode setting.

BM2_4

Explains BM2 dip switches for outdoor unit wireless module MAC address and clearing EEPROM data.

BM3 introduction

BM3_1

Details BM3 dip switches for outdoor type selection.

BM3_5

Details BM3 dip switches for outdoor horse power setting.

BM4 introduction: Group class (physical master unit is valid)

BM4_1

Explains BM4 dip switches for ModeBus protocol selection.

BM4_4

Explains BM4 dip switches for ModeBus communication address settings.

Outdoor unit digital tube display settings

Outdoor unit digital tube display settings (Continuation)

System status display and control (host) (Continuation)

â‘£ E2 control parameters display and setting

Guides on setting E2 control parameters, including setting methods and notes on automatic operation.

2. Valve box PCB photo and dip switch setting

SW03 is used for valve box address setting

SW03_1

Explains SW03 usage for setting valve box addresses automatically or via dip switch.

SW03_3 ~ SW03_8 Set the communication address with dip switch

SW03_3 ~ SW03_8

Provides a detailed table for setting communication addresses using SW03 dip switches.

SW03_3 ~ SW03_8 (Continuation)

SW03_3 ~ SW03_8 (Continuation)

Continues the table for setting communication addresses using SW03 dip switches.

SW1 sets the communication address between the valve box and the indoor unit 1.

SW1 sets the communication address between the valve box and the indoor unit 1.

Explains how SW1, SW2, SW3, and SW4 are used to set communication addresses for indoor units connected to the valve box.

3. Control function (Continuation)

3.1 Compressor control

Continues compressor control details, covering crankcase heater and start protection.

3.4 Pressure control

Details high and low pressure control in cooling and heating modes, including setting values.

3.10 High pressure protection control in heating

Explains how high pressure is detected and used to control compressor capacity to prevent high pressure rise.

3.11 Current safety control

Details control actions when compressor current exceeds limits, including frequency reduction and stopping.

4. Failure code

Outdoor unit failure code

Lists outdoor unit failure codes and their corresponding descriptions, including sensor failures and communication issues.

Outdoor unit failure code (Continuation)

Outdoor unit failure code (Continuation)

Continues the list of outdoor unit failure codes, covering fan motor module radiator temp. too high.

6. Sensor resistance table

R80=50 kΩ±3% B25;80=4450 K±3%

R25=10 kΩ±3% B25;50=3700 K±3%

R25=10 kΩ±3% B25;50=3700 K±3% (Continuation)

R80=50 kΩ±3% B25;80=4450 K±3% (Continuation)

Smartlink benefits

7.4 The installation requirement of Smartlink

7.5 The debugging guidance of Smartlink

Each system can finish automatic networking debugging separately, as shown in the left debugging chart.

Haier MRV 5-RC AD162MJERA Specifications

General IconGeneral
BrandHaier
ModelMRV 5-RC AD162MJERA
CategoryHeat Pump
LanguageEnglish

Related product manuals