DIP Switch Settings
Description SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8
Capacity: 9000btu/h OFF OFF OFF --- --- --- --- ---
Capacity: 12000btu/h ON OFF OFF --- --- --- --- ---
Capacity: 18000btu/h OFF ON OFF --- --- --- --- ---
Capacity: 24000btu/h ON ON OFF --- --- --- --- ---
Room card invalid --- --- --- OFF* --- --- --- ---
Room card valid --- --- --- ON --- --- --- ---
Heat pump --- --- --- --- OFF* --- --- ---
Cooling only --- --- --- --- ON --- --- ---
Fresh air valid --- --- --- --- --- OFF* --- ---
External alarm output --- --- --- --- --- ON --- ---
Without filter clean warning --- --- --- --- --- --- OFF* ---
With filter clean warning --- --- --- --- --- --- ON ---
North America area --- --- --- --- --- --- --- OFF*
Non-North America area --- --- --- --- --- --- --- ON
Description SW3-1 SW3-2 SW3-3 SW3-4
Special fresh air (Canadian ventilation mode, Canada particular Area) invalid OFF* --- --- ---
Special fresh air (Canadian ventilation mode, Canada particular Area) valid ON --- --- ---
Console/MESP Duct --- OFF* --- ---
Cassette (Reserved) --- ON --- ---
Auxiliary heater invalid --- --- OFF* ---
Auxiliary heater valid --- --- ON ---
ESP grade 0-4 level --- --- --- OFF
ESP grade 0-10 level --- --- --- ON*
SW1 DIP Switch Settings
SW3 DIP Switch Settings
*Factory Default Setting
*Factory Default Setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier USYM12UCDSA and is the answer not in the manual?

Haier USYM12UCDSA Specifications

General IconGeneral
BrandHaier
ModelUSYM12UCDSA
CategoryHeat Pump
LanguageEnglish

Related product manuals