8.3 Daily maintenance
In order to ensure the good performance of the equipment and to prolong its service life, it is
necessary to carry out maintenance on the equipment at a frequency of once a week.
Inspection of the condenser, checking that the air ducts are not blocked by foreign objects
and that the incoming and outgoing air around the equipment is clear;
Cleaning of the condenser and cleaning of dust screens;
Check the cooling medium for foreign objects, microorganisms, etc., and replace the
cooling medium in 15-20 days. the cooling medium must be pure, distilled or high purity water;
Checking water connections for looseness and pump leaks;
Inspection of the water tank and cleaning of the dirt deposited inside the tank;
Regularly clean the filter in the waterway of the equipment, generally 7~10 days to clean
the filter, the company commonly usedof filters, as shown in Figure 13, with the Y-filter placed
at the suction of the pump or at the outlet of the equipment;
Testing insulation resistance, insulation resistance 5 MΩ;
Check earth resistance, earth resistance 4Ω;
Capacitance tests are carried out on the capacitors of the compressor and fan. Capacitance
decreases of more than 10% require replacement of the capacity
Fig. 13 Filters commonly used in our company
Filter
Filter element
Screw cap
Y type filter