3
Parameter Operation description
● POWER ON DELAY
● uses 1 set time (set time displayed on SV display)
● when power is applied, output turns OFF, timing starts
● when displayed time reaches set time, output turns ON,
displayed time is held (ONE-SHOT output selectable)
POND
● POWER ON FLICKER - OFF START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV
display, Ton set time displayed on SV display)
● when power is applied, OFF timing starts
● when displayed time reaches Toff set time, output turns ON,
after displayed time initialization ON timing starts
● when displayed time reaches Ton set time, output turns OFF,
after displayed time initialization OFF timing starts
● output repeats ON/OFF operations according to Ton and Toff
set times
PFKF
● POWER ON FLICKER - ON START
● uses 2 set times, Ton and Toff (Ton set time displayed on PV
display, Toff set time displayed on SV display)
● when power is applied, output turns ON, ON timing starts
● when displayed time reaches Ton set time output turns OFF,
after displayed time initialization OFF timing starts
● when displayed time reaches Toff set time, output turns ON,
after displayed time initialization ON timing starts
● output repeats ON/OFF operations according to Ton and Toff
set times
PFKN
● POWER ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● when power is applied, output turns ON, timing starts
● when displayed time reaches set time, output turns OFF,
displayed time is held
PINT
● TWIN - ON START
● uses 2 set times, Ton and Toff (Ton set time displayed on PV
display, Toff set time displayed on SV display)
● when power is applied, OUT1 output turns OFF, OUT2 output
turns ON, ON timing starts
● when displayed time reaches Ton set time OUT1 output turns
ON, OUT2 output turns OFF, after displayed time initialization
OFF timing starts
● when displayed time reaches Toff set time, OUT1 output turns
OFF, holds output and displayed time
TWON
● TWIN - OFF START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV
display, Ton set time displayed on SV display)
● when power is applied, OUT1 and OUT2 outputs turn OFF, OFF
timing starts
● when displayed time reaches Toff set time, OUT2 output turns
ON, after displayed time initialization ON timing starts
● when displayed time reaches Ton set time, OUT1 output turns
ON, holds output and displayed time
TWOF
● STAR – DELTA
● uses 2 set times, Ton and Toff (Ton set time displayed on PV
display, Toff set time displayed on SV display)
● when power is applied, OUT1 output turns OFF, OUT2 output
turns ON, ON timing starts
● when displayed time reaches Ton set time, OUT2 output turns
OFF, after displayed time initialization OFF timing starts
● when displayed time reaches Toff set time, OUT1 output turns
ON, holds output and displayed time
● OUT1 operates as '
Δ
' output, OUT2 operates as ' ' output.
● Toff set time is '
Δ -
' operation switching time
S - D
Parameter Operation description
● SIGNAL ON DELAY
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, timing starts (START signal holds ON status )
● when displayed time reaches set time output turns ON, holds output and
displayed time (ONE-SHOT output selectable)
● When START signal is cancelled, initializes output and displayed time
SOND
● SIGNAL ON FLICKER - OFF START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV display, Ton
set time displayed on SV display)
when START signal is applied,OFF timing starts (START signal holds ON status)
● when displayed time reaches Toff set time, output turns ON, after displayed
time initialization ON timing starts
● when displayed time reaches Ton set time output turns OFF, after displayed
time initialization OFF timing starts
● output repeats ON/OFF operations according to Ton and Toff set times
● when START signal is cancelled, initializes output and displayed time
SFKF
● SIGNAL ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● When START signal is applied, output turns ON, timing starts (START signal
holds ON status )
when displayed time reaches set time output turns OFF,displayed time is held
● When START signal is cancelled, initializes output and displayed time
SINT
● SIGNAL ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● When START signal is applied, output turns ON, timing starts (START signal
holds ON status )
when displayed time reaches set time, output turns OFF, displayed time is held
● when START signal is cancelled, initializes output and displayed time
SNFN
● SIGNAL ON/OFF DELAY - OFF START
● uses 2 set times, Ton and Toff (Ton set time displayed on PV display, Toff
set time displayed on SV display)
● when START signal is applied, ON timing starts
when displayed time reaches Ton set time output turns ON,displayed time is held
When START signal is cancelled, output holds ON output status,OFF timing starts
● when displayed time reaches Toff set time output turns OFF, displayed
time is held
SNFF
● SIGNAL OFF DELAY
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, output turns ON (START signal holds ON
status )
● when START signal is cancelled, holds output and timing starts
when displayed time reaches set time output turns OFF, displayed time is held
● when START signal is cancelled, initializes output and displayed time
SOFD
● SIGNAL TRIGGER ON DELAY
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, timing starts
● when displayed time reaches set time output turns ON, holds output and
displayed time (ONE-SHOT output selectable)
● when START signal is repeatedly applied, only uses the first START signal
S.OND
● SIGNAL TRIGGER ON FLICKER - ON START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV display, Ton
set time displayed on SV display)
● when START signal is applied, output turns ON, ON timing starts
● when displayed time reaches Ton set time output turns OFF, after displayed
time initialization OFF timing starts
● when displayed time reaches Toff set time, output turns ON, after displayed
time initialization ON timing starts
● output repeats ON/OFF operations according to Ton and Toff set times
● When START signal is repeatedly applied, only uses the first START signal
S.FKN
● SIGNAL TRIGGER ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, output turns ON, timing starts
when displayed time reaches set time output turns OFF, displayed time is held
● When START signal is repeatedly applied, only uses the first START signal
● after reaching set time, when START signal is applied,
output turns ON, and after time value initialization timing starts
S.INT
● SIGNAL TRIGGER ON DELAY – RESET
● when START signal is applied, timing starts
● when displayed time reaches set time, output turns ON, holds output and
displayed time (ONE-SHOT output selectable)
● when START signal is re-applied during timing, timing starts after displayed
time initialization
S.ODR
Operation overview
󱇧 LT4 󱇧 LT4S