Installation
Draft Test Procedure
Aftertheventingiscompleted,thereboxdraftwillneedto
becheckedandpossiblyadjusted.Afterremovingtheplug
boltfromthedrafthole(3/16”hexkeywrench)showninFig.
9,insertthedraftmetertube.Thehopperlidmustbelatched
duringthistest.(Itisrecommendedthatthedraftmeterhave
ascaleof0to1”WC.)
Turnthefeedadjusterto“Test”.Thiswillstartthecombustion
blowerand allow youto check andrecord the HighDraft
______-IWCdate_______Themaximumdraftallowedis
-.9”WaterColumn(-224Pa).Thereisnoadjustmentforthe
HighDraft,otherthanre-positioningthecombustionblower
fanbladeonitsshaft,orachangeintheventingconguration.
After the first 60seconds the “Test” mode lowers the
combustionblowervoltagetotheLowBurnvoltage.During
thisloweredvoltagecycle,theLow Draft must be checked
andadjustedifnecessary.Therecommendedlowdraftsetting
shouldbebetween -.45 and-.55IWC.Depending on the
amountofverticalrise,itmaynotbepossibletogetalow
draftreadinginthisrange.Inthiscase,re-positioningthefan
bladefurtheronthemotorshaftmaybehelpful.
Thereisalowdraftvoltageadjustmentscrewlocatedthrough
thesmallholetotherightoftheIgniterLight.SeeFig.10.
AdjustedLowDraftis __________ -IWC.Toincreasethe
draftinhigheraltitudes,HighAltitudekit#1-00-232059may
beneeded.
Don’t forget to turn the feed adjuster off of “Test”, and
reinstall the draft test plug bolt into the boiler.
Fig. 9
“Test”
Low Draft
Adjustment Pot
Fig. 10
Draft
Testing Port
High altitude kit #1-00-232059.
Installthisringtoincreasedraftinhigheraltitude
installation locations.
CAUTION
Hot While In Operation. Do Not Touch. Keep Children,
Clothing And Furniture Away. Contact May Cause Skin
Burns. See Nameplate And Instructions.
Keep Doors Closed During Operation.
WARNING
Do Not Store Fuel or Other Combustible Material
Within Installation Clearance Area.
WARNING
Risk of Fire - Do Not Operate With the Flue Draft
Exceeding -.9” Water Column (-224 Pa).