Harman®  •  P-Series Installation Manual_R18  •  2014 - ___  •  06/1816 3-90-436168i
Harman pellet stoves depend on a combustion fan to pull air 
through the unit for combustion. The venting system restricts 
the ability of the combustion fan to move the required amount 
of air through the unit. A system with too much resistance 
will result in incomplete combustion, more frequent required 
cleaning and poor unit performance. It is always best to 
choose a location for the appliance that will result in a venting 
system with the shortest equivalent vent length (EVL).
It is best to have your venting system designed by a Harman 
authorizeddealerbeforeyounalize your purchase of an
appliance. 
Equivalent Vent Length: The equivalent vent length for 
common pellet vent components are:
• 90° Elbows or Tee: 5 EVL Units
• 45° elbow: 3 EVL Units
• Vertical Pipe or Liner: ½ EVL Unit
• Horizontal Pipe or liner: 1 EVL Unit
The total allowable equivalent vent length is:
• 20 EVL for 3” pellet vent pipe or liner
• 30 EVL for 4” pellet vent pipe or liner
Duetothepotentialfor y ash accumulation in horizontal
venting sections, the maximum permissible horizontal venting 
length is:
• 4 ft. for 3” & 4” pellet vent pipe.
C. Venting & Use of Elbows
O
+
= Positive static pressure
=  Negative static pressure
O
-
Figure 4.11
+
+
Example: First Floor Installation
A unit is to be installed using 3” Pellet Pipe with 3 feet 
of horizontal pipe, a Tee, 10 feet of vertical pipe, a 90° 
elbow and a termination cap.
The equivalent vent length is:
3 ft. of Horizontal Pipe (1 x 3 EVL)  = 3 EVL
90° Elbow or Tee (1 x EVL)    = 5 EVL
10 ft. of Vertical Pipe (10 x .5 EVL)  = 5 EVL
90° Elbow or Tee (1 x EVL)    = 5 EVL
Termination Cap      = 0 EVL
Equivalent Vent Length      = 18 EVL
In the example system detailed above, the EVL was 138 
which is less than the maximum of 20 EVL for 3” pellet 
ventpipe,thusthisisasatisfactoryventingconguration.
Example: Connection to Masonry Chimney
A unit is to be installed using 3” Pellet Pipe with 2 feet of 
horizontal pipe, a Tee, 4 feet of vertical pipe, an elbow, a 
Tee, 21 feet of vertical liner, and a termination cap.
The equivalent vent length is:
2 ft. of Horizontal Pipe (1 x 2 EVL)  = 2 EVL
90° Tee (1 x 5 EVL)      = 5 EVL
4 ft. of Vertical Pipe (4 x .5 EVL)   = 2 EVL
90° Elbow (1 x 5 EVL)      = 5 EVL
90° Tee (1 x 5 EVL)      = 5 EVL
21 ft. of Vertical Liner (21 x .5 EVL)  = 10.5 EVL
Termination Cap      = 0 EVL
Equivalent Vent Length      = 29.5 EVL
In the example system detailed above, the EVL was 
29.5 which exceeds the maximum of 20 ft. for 3” pellet 
vent pipe, thus 3” vent pipe should not be used in this 
installation. However, since 4” pipe can support an EVL 
up to 30, the use of 4” pipe would create a satisfactory 
installation.