10P 6 1 A P ellet S tove
3 -9 0 -0 5 8 2 2 R 2 8 _ 0 8 /1 3
# 2 Preferred method
This method also provides excellent venting for normal
operation but requires the stove to be installed farther from
the wall. The vertical portion of the vent should be three to
ve feet high and at least three inches from a combustible
wall. This vertical section will provide natural draft in the event
of a power failure.
If the stove is installed below grade be sure the vent
termination is at least 12" above grade. The outlet must also
be 1 foot from the house/building.
Note: Do not place joints within wall pass-throughs.
# 1 Preferred method
This method provides excellent venting for normal operation
and allows the stove to be installed closest to the wall. Two
inches from the wall is safe however, four inches allows
better access to remove the rear panel. The vertical portion of
the vent should be three to ve feet high. This vertical section
will help provide natural draft in the event of a power failure.
Note: Do not place j oints within wall pass-throughs.
V enting
F ig. 8
3 ft.
to combustibles
3 ft.
to
combustibles
F ig. 9
3 ft.
to combustibles
3 ft.
to
combustibles
36" min
clearance to any
combustible
material
12" min. wall to outlet
CAUTION
K eep combustible materials (such as grass, leaves, etc.) at
eat eet aay rm te ue utet n te ute te
building.