Water in temp.
sensor failure
The sensor is open or
short circuit
Check or replace a new sensor
Water out temp.
sensor failure
The sensor is open or
short circuit
Check or replace a new sensor
Coil sensor failure
(heating mode)
The sensor is open or
short circuit
Check or replace a new sensor
Gas return sensor
failure
The sensor is open or
short circuit
Check or replace the sensor
Ambient temp. is
below 8 or the sensor
is open or short circuit
Stop the unit when ambient is
below 8 Check or replace the
sensor
℃
Temp. too much
difference between
water-in and water-out
Water volume is not
enough
Anti -freezing under
cooling mode
The first time freezing
protection in winter
The second time
freezing protection in
winter
Coil sensor failure
(cooling mode)
The sensor is open
or short circuit
Check or change the sensor
Refrigerant system
pressure is high
Check pressure gauge,
increase the water volume
Refrigerant system
pressure is low
Check pressure gauge, refeed
refrigerant
No water/little water
in water system.
Check the water flow volume,
water pump failure or not
Power supply
connections wrong
(for 3phase unit)
Wrong phase or
lack of phase power
connection
Check connections of power
cable
3times display PP06
(temp. too much
difference between
water-in&out) in 30 min
Water flow volume
not enough, water
pressure difference is
too low
Check the water flow volume,
or water system is jammed or
not
Wire controller and
the PCB connection
failure
Check the wire connection