What to do if my Hayward Energyline Pro Inverter Heat Pump shows high pressure protection?
- JJennifer WilcoxAug 21, 2025
To address high pressure protection issues with your Hayward Heat Pump, several factors should be verified. Begin by checking the water flow and ensuring the water flow detector is functioning correctly. Inspect the valve opening and by-pass to confirm they are properly adjusted. Make sure the evaporator is not clogged. Verify that the water temperature isn't too high. If the issue occurred after maintenance, empty and evacuate the cooling circuit to eliminate any incondensable problems. If the fluid load is too high, remove fluid into a liquid bottle.