USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Page 16 of 36 2.70 THP VS Pump Family IS3206VSP3 Rev-B
DIP SWITCH STATUS
PUMP ADDRESS #1 #2 #3 #4 #5
Pool Filte
OF
OF
OF
OF
OF
Aux 1 / Spa Filte
OF
ON OF
OF
OF
Aux 2 OF
OF
ON OF
OF
Aux 3 OF
ON ON OF
OF
Aux 4 OF
OF
OF
ON OF
Aux 5 OF
ON OF
ON OF
Aux 6 OF
OF
ON ON OF
Aux 7 OF
ON ON ON OF
Aux 8 OF
OF
OF
OF
ON
Aux 9 OF
ON OF
OF
ON
Aux 10 OF
OF
ON OF
ON
Aux 11 OF
ON ON OF
ON
Aux 12 OF
OF
OF
ON ON
Aux 13 OF
ON OF
ON ON
Aux 14 OF
OF
ON ON ON
Lights Button OF
ON ON ON ON
5.3. External Relay Speed Control Wiring (Optional, for remote selection of pump speed)
Note: For third party controls and Hayward controls that are NOT software compatible.
Figure 5.3-1
Connection wire must be rated for a minimum of 300V. Inputs are rated to accept a low voltage supply of 18-30 VAC,
9-30 VDC, 50/60 Hz. The “+12V” and “COM” terminals may be used as a low voltage supply, however, these
terminals also supply power to the user interface, so care must be taken when connecting to these terminals to
ensure proper operation of the user interface. DIP switch #1 must be “ON”.