EasyManua.ls Logo

Heat Controller GDD95A - Alternate Method of Providing Air from Outside; Conventional Vent Systems - Unconfined Spaces; Category IV Venting

Heat Controller GDD95A
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Alternate Method of Providing Air from
Outside
If acceptable under local Codes, it is permitted to provide
outside air using one opening (See NFGC). Generally,
con๏ฌned spaces must have two openings in the space for
combustion air. One opening must be within 12 inches of
the ceiling, and the other must be within 12 inches of the
๏ฌ‚oor. However, an alternative method recently adopted by
the NFGC uses one opening within 12 inches of the top
of the space. This method may be used if it is acceptable
to the local codes.
THE FOLLOWING CONDITIONS MUST BE MET:
1. The opening must start within 12โ€ of the top of the
structure and connect with the out of doors through
vertical or horizontal ducts or be ducted to a crawl or
attic space that connects with the out of doors.
2. The opening must have a minimum free area of 1 sq.
in. per 3,000 Btu per hour of the total input rating of all
equipment located in the enclosure.
3. The free area must not be less than the sum of all the
areas of the vent connectors in the enclosure.
๎˜ฃ๎™๎™Ž๎™–๎™…๎™Ž๎™”๎™‰๎™๎™Ž๎™๎™Œ๎˜€ ๎˜ถ๎™…๎™Ž๎™”๎˜€ ๎˜ณ๎™™๎™“๎™”๎™…๎™๎™“๎˜€ ๎˜๎˜€ ๎˜ต๎™Ž๎™ƒ๎™๎™Ž๎™ฌ๎™Ž๎™…๎™„๎˜€
๎˜ณ๎™๎™๎™ƒ๎™…๎™“
An uncon๏ฌned space is an area including all rooms not
separated by doors with a volume greater than 50 cubic
feet per 1,000 Btuh of the combined input rates of all
appliances which draw combustion air from that space.
In general, a furnace installed in an uncon๏ฌned space will
not require outside air for combustion. However, in homes
built for energy ef๏ฌciency (low air change rates), it may
be necessary to provide outside air to ensure adequate
combustion and venting, even though the furnace is located
in an uncon๏ฌned space. See Example below.
EXAMPLE
A space with a water heater rated at 45,000 Btuh
input and a furnace rated at 75,000 Btuh requires a
volume of 6,000 cubic feet [50 x (45 + 75) = 6,000] to
be considered uncon๏ฌned. If the space has an 8 foot
ceiling, the ๏ฌ‚oor area of the space must be 750 sq. ft.
(6,000 / 8 = 750).
๎˜ฃ๎™๎™”๎™…๎™‡๎™๎™’๎™™๎˜€๎˜ฉ๎˜ถ๎˜€๎˜ถ๎™…๎™Ž๎™”๎™‰๎™Ž๎™‡
WARNING:
๎˜ต๎™๎™๎™Ž๎˜€ ๎™ƒ๎™๎™๎™๎™Œ๎™…๎™”๎™‰๎™๎™Ž๎˜€ ๎™๎™†๎˜€ ๎™”๎™ˆ๎™…๎˜€ ๎™†๎™•๎™’๎™Ž๎™๎™ƒ๎™…๎˜€ ๎™‰๎™Ž๎™“๎™”๎™๎™Œ๎™Œ๎™๎™”๎™‰๎™๎™Ž๎˜Œ๎˜€
๎™ƒ๎™๎™’๎™…๎™†๎™•๎™Œ๎™Œ๎™™๎˜€ ๎™‰๎™Ž๎™“๎™๎™…๎™ƒ๎™”๎˜€ ๎™”๎™ˆ๎™…๎˜€ ๎™…๎™Ž๎™”๎™‰๎™’๎™…๎˜€ ๎™ญ๎™•๎™…๎˜€ ๎™“๎™™๎™“๎™”๎™…๎™๎˜€ ๎™‚๎™๎™”๎™ˆ๎˜€
๎™‰๎™Ž๎™“๎™‰๎™„๎™…๎˜€ ๎™๎™Ž๎™„๎˜€ ๎™๎™•๎™”๎™“๎™‰๎™„๎™…๎˜€ ๎™”๎™ˆ๎™…๎˜€๎™†๎™•๎™’๎™Ž๎™๎™ƒ๎™…๎˜€ ๎™”๎™๎˜€ ๎™๎™“๎™“๎™•๎™’๎™…๎˜€ ๎™‰๎™”๎˜€๎™‰๎™“๎˜€
๎™๎™’๎™๎™๎™…๎™’๎™Œ๎™™๎˜€๎™“๎™…๎™๎™Œ๎™…๎™„๎˜Ž๎˜€๎˜ฌ๎™…๎™๎™‹๎™“๎˜€๎™‰๎™Ž๎˜€๎™”๎™ˆ๎™…๎˜€๎™ญ๎™•๎™…๎˜€๎™“๎™™๎™“๎™”๎™…๎™๎˜€๎™ƒ๎™๎™Ž๎˜€
๎™’๎™…๎™“๎™•๎™Œ๎™”๎˜€๎™‰๎™Ž๎˜€๎™“๎™…๎™’๎™‰๎™๎™•๎™“๎˜€๎™๎™…๎™’๎™“๎™๎™Ž๎™๎™Œ๎˜€๎™‰๎™Ž๎™Š๎™•๎™’๎™™๎˜€๎™๎™’๎˜€๎™„๎™…๎™๎™”๎™ˆ๎˜€๎™„๎™•๎™…๎˜€
๎™”๎™๎˜€๎™…๎™˜๎™๎™๎™“๎™•๎™’๎™…๎˜€๎™๎™†๎˜€๎™ญ๎™•๎™…๎˜€๎™๎™’๎™๎™„๎™•๎™ƒ๎™”๎™“๎˜Œ๎˜€๎™‰๎™Ž๎™ƒ๎™Œ๎™•๎™„๎™‰๎™Ž๎™‡๎˜€๎™ƒ๎™๎™’๎™‚๎™๎™Ž๎˜€
๎™๎™๎™Ž๎™๎™˜๎™‰๎™„๎™…๎˜Ž
This furnace is classi๏ฌed as a โ€œCategory IVโ€ appliance,
which requires special venting materials and installation
procedures. This section speci๏ฌes installation requirements
for Conventional (1-pipe) and Direct Vent (2-pipe) piping.
For 1- pipe installations, install vent piping as described in
this section and provide air for combustion and ventilation
according to page 7, page 8, page 9 & page 10.
The length of vent and combustion air piping for either
type of installation are llisted in Table 1.
FURNACE
MODELS
(BTU)
FURNACE
INSTALLATION
SINGLE VENT PIPE LENGTH (FT.)
WITH 1 LONG RADIUS ELBOWโ€ 
DUAL VENT PIPE LENGTH (FT.)
WITH 1 LONG RADIUS ELBOW ON EACH PIPEโ€ 
OUTLET
2โ€ DIAMETER
OUTLET
3โ€ DIAMETER
๎˜ฉ๎˜ฎ๎˜ฌ๎˜ฅ๎˜ด๎˜€๎˜๎˜€๎˜ฏ๎˜ต๎˜ด๎˜ฌ๎˜ฅ๎˜ด
2โ€ DIAMETER
๎˜ฉ๎˜ฎ๎˜ฌ๎˜ฅ๎˜ด๎˜€๎˜๎˜€๎˜ฏ๎˜ต๎˜ด๎˜ฌ๎˜ฅ๎˜ด
3โ€ DIAMETER
38,000 Up๏ฌ‚ow 50 70 50 70
54,000
Up๏ฌ‚ow 70 90 70 90
Down๏ฌ‚ow 70 90 70 90
72,000
Up๏ฌ‚ow 50 90 50 90
Down๏ฌ‚ow 50 90 50 90
90,000
Up๏ฌ‚ow 60 90 60 90
Down๏ฌ‚ow 60 90 60 90
108,000 Up๏ฌ‚ow N/A 90 N/A 90
118,000 Down๏ฌ‚ow N/A 90 N/A 90
120,000
Up๏ฌ‚ow N/A 90 N/A 90
Down๏ฌ‚ow N/A 90 N/A 90
โ€ 
NOTES:
1. Subtract 2.5 ft. for each additional 2 inch long radius elbow, 5 ft. for each additional 2 inch short radius elbow, 3.5 ft. for each additional 3 inch long radius elbow,
and 7 ft. for each additional 3 inch short radius elbow. Subtract 5 ft for each 2โ€ tee and 8 ft for each 3โ€ tee.
2. Two 45 degree elbows are equivalent to one 90 degree elbow.
3. This table applies for elevations from sea level to 2,000 ft. For higher elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.
4. A long radius elbowโ€™s centerline radius is equal to or greater than 1.5 times the vent diameter.
๎˜ด๎™๎™‚๎™Œ๎™…๎˜€๎˜‘๎˜Ž๎˜€๎˜ถ๎™…๎™Ž๎™”๎˜€๎˜ฐ๎™‰๎™๎™…๎˜€๎˜ฌ๎™…๎™Ž๎™‡๎™”๎™ˆ๎™“

Table of Contents

Other manuals for Heat Controller GDD95A

Related product manuals