EasyManua.ls Logo

Heat Controller RSE1318-1A - System Specifications and Installation Preparation; General Information and Application; Unit Location, Mounting, and Securing

Heat Controller RSE1318-1A
23 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
TABLE 1
ELECTRICAL AND PHYSICAL DATA
NOTE: Factory Refrigerant Charge includes refrigerant for 15 feet of standard line set.
Electrical Data Physical Data
Cooling
Capacity
Phase-Frequency
Voltage
(Hz) (Volts)
Compressor
Rated Load
Amperes
(RLA)
Compressor
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Minimum
Amperes
Maximum
Amperes
Outdoor
Coil
Area
Sq. Ft.
[Sq. M]
Outdoor
Coil
No.
Rows
Outdoor
Coil
CFM
[L/s]
Refrigerant
Charge
oz.
[g]
Net
Weight
lb.
[kg]
Ship
Weight
lb.
[kg]
Fuse or HACR
Circuit Breaker
18 1-60-208/230 6.4/6.4 36 1 10/10 15/15 15/15 8.43 1 1900 67.4 150 158
[.78] [897] [1899] [68.0] [71.7]
24 1-60-208/230 9.9/9.9 54 0.6 14/14 20/20 20/20 11.06 1 1700 77.0 155 163
[1.03] [802] [2183] [70.3] [73.9]
30 1-60-208/230 10.6/10.6 61 0.8 15/15 20/20 20/20 13.72 1 2325 97.8 175 185
[1.30] [1097] [2778] [79.4] [83.0]
36 1-60-208/230 13.5/13.5 78 0.8 18/18 25/25 30/30 16.39 1 2800 108.0 200 212
[1.52] [1321] [3062] [90.7] [96.1]
42 1-60-208/230 19.2/19.2 105 0.8 25/25 30/30 40/40 16.39 1 2800 121.0 205 217
[1.52] [1321] [3430] [93.0] [98.4]
48 1-60-208/230 21.1/21.1 115 1.2 28/28 35/35 45/45 16.39 1 3300 122.8 210 222
[1.52] [1557] [3487] [95.3] [100.7]
60 1-60-208/230 25/25 150 1.2 33/33 40/40 50/50 21.85 1 3575 190.8 247 258
[2.03] [1687] [5415] [112.0] [117.0]

Related product manuals