REPLACEMENT UNITS
To prevent failure of a new condensing unit, the existing evaporator tubing system
must be correctly sized and cleaned or replaced. Care must be exercised that the
expansion device is not plugged. Test the oil for acid. If positive, a suction line filter
drier is mandatory. For new and replacement units, a liquid line filter drier should be
installed and refrigerant tubing should be properly sized.
INTERCONNECTING TUBING
VAPOR AND LIQUID LINES
Keep all lines sealed until connection is made.
Refer to Line Size Information in Tables 3 through 5 for correct size and multipliers to
be used to determine capacity for various vapor line diameters and lengths of run.
The losses due to the lines being exposed to outdoor conditions are not included.
The factory refrigeration charge in the outdoor unit is sufficient for 15 feet of inter-
connecting lines. The factory refrigeration charge in the outdoor unit is sufficient for
the unit and 15 feet of standard size interconnecting liquid and vapor lines. For dif-
ferent lengths, adjust the charge as indicated below.
1/4” ± .3 oz. per foot
5/16” ± .4 oz. per foot
3/8” ± .6 oz. per foot
1/2” ± 1.2 oz. per foot
MAXIMUM LENGTH OF LINES
The maximum length of interconnecting line is 150 feet. Always use the shortest
length possible with a minimum number of bends. Additional compressor oil is not
required for any length up to 150 feet.
NOTE: Excessively long refrigerant lines cause loss of equipment capacity.
FIGURE 2
TIE-DOWN KIT ASSEMBLY
DETAIL A