EasyManua.ls Logo

Hekatron FSZ Basis - Page 29

Hekatron FSZ Basis
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
9 Electrical installation
LED
green
LED
orange
LED
red
THM Relay Condition Possible cause Remedy
ON Flashes
3 x
OFF OFF OFF Fault in the
manual release
button loop
System with line surveil-
lance:
Missing termination mod-
ule AM 142 or wrong DIP
switch setting or short-
circuit of the connection
line of the external HAT.
System with line
surveillance:
Connect the termina-
tion module AM 142
or set the DIP switches
according to the circuit
configuration or check
and reconnect the lines.
ON Flashes
4 x
OFF OFF OFF Excess tempera-
ture in FSZ Basis
Ambient temperature
too high
Reduce the ambient
temperature
ON Flashes
5 x
OFF OFF OFF Fault in the
loop of the
electromagnetic
door retainer
Short-circuit of the con-
nection line of the THM
Check and reconnect
the lines
ON Flashes
6 x *
Flashes
6 x *
OFF OFF Fault
Keypad
The keypad is improperly
connected
Pull off the plug from the
keypad and reconnect it
ON Flashes
9 x
OFF OFF OFF Fault
Output current
Number of connected
consumers too high
Recalculate the total
current of the consumers
and re-erect the system
ON Flashes
10 x
OFF OFF OFF Fault at FSZ
Basis
Short-circuit of the 24-V
supply
Check the wiring
* Whether only one LED or both LEDs are flashing, depends on how the keypad is improperly connected.