EasyManua.ls Logo

Heraeus HS 15 - Page 192

Default Icon
282 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Testing Safety Cabinet Class II according to EN 12 469
Testing HS / HSP Ingo Nierobisch 14.06.02
HS / HSP
Visual check
Labels, warnings
Scratches
Exhaust connection
Options
Electrical safety test ( VDE )
Ground conductor ( Schutzleiter )
Insulation resistance ( Isolationswiderstand )
Leakage current ( Ableitstrom )
Air direction test
Adjust front window to working position ( 200 mm )
Slide along the window opening with smoke tube
Air flow direction from outside to inside
( no refluxing, no visible turbulence )
Inflow air velocity test
Inflow air speed (method 1)
Adjust front window to an opening of 5 cm
Measuring air velocity in the middle in steps of
10 cm (start with 5 cm) __
Inflow air can be calculated: v
2
= v
2
/ 4
Exhaust air speed (method 2)
Place the measuring frame over the exhaust
filter opening and seal with adhesive tape
Measure air velocity according to 5-position
method
Inflow air can be calculated: v
2
= v
1
x A
1
/A
2
Laminar air flow test
Cabinet in operation ( at least 20 min.)
Adjust anemometer 5 cm above front window
opening
Measuring grid: of the edge 15 cm,
between measure point 30 cm
Measure air velocity (wait 1 min.)
Mean value of air velocity: 0,25 - 0,5 m/s +
20 %
If air velocity is too low, test the following:
Voltage of the fans
Exhaust connection
Ducting system
Filter leakage test (DEHS- test)
Main filter and exhaust filter
Turn cabinet on
Calibrate particle counter
Place aerosol generator in the cabinet
Connect rarefaction between particle counter and
test connection (under working plate)
Only HSP: Remove rubber seal from bypass opening
Switch on aerosol generator
Measure particles at the dirty side of main or exhaust
filter, 5 measurements (each for 1 min)
Required value: 30 mil. particles of size 0.3 µm
Disconnect the particle counter from the rarefaction
and connect to the measuring-head
Scan the seat of the sealing an the clean side of the
main filter. Speed of scanning < 5 cm/sec, distance
max. 1 cm.
Limit value of particles > 300 St./ 0.3 µm
If max. number of particles is exceeded change filter.
Monitoring equipment, acoustic and visual alarm
Cabinet in operation
Measure fan voltage
Perform test for laminar air ( mean value 0,40 m/s )
Adjust lower limit pressure switch
Find out point with lowest air velocity
Set anemometer in this point, measure air
velocity
Set fan voltage so that at this measuring point air
velocity is mean value -20 % ( 0,32 m/s )
Change adjustment of lower pressure switch it
just turns on. Visual and acoustic alarm goes on
Adjust upper limit pressure switch
Find out point with highest air velocity
Set anemometer in this point, measure air
velocity
Set fan voltage so that at this measuring point air
velocity is mean value +20 % ( 0,48 m/s )
Change adjustment of upper pressure switch it
just turns on. Visual and acoustic alarm goes on
Return fan voltage to the measured value
Turn cabinet off and on, check operation
Fill out test protocol and paste up inspection sticker
Additional: KI-Discus test (personnel protection test)
Cabinet in operation (at least 20 min)
Reduce air movements in laboratory ( close doors,
windows, air condition, ... )
Install KI-Discus equipment according to its operating
instruction
Do measurement 5 times according to instruction
Count potassium iodide particles on filter paper
Calculate protection factor
Limit < 60 particles
For deviations: repeat measurement 2 times
Check air flow in laboratory, check filter sealing

Related product manuals