DIMENSIONS, WIRING AND MECHANICAL PARTS | PAG. 14
The equipment must be isolated or disconnected before connecting the voltage
input for the generator, as there is a risk of danger. The USB connector complies
with the standard 2.0.
To power the control panel, it is recommended to use a 1mm2 section cable. A
cable with a diameter of 2.5 mm2 must be used for +BAT, ARR, PR and PC con-
nections. For all other connections, it is recommended to use a 1mm2 cable
diameter.
5.1 INPUTS AND OUTPUTS
Signal Description Type Characteristics
Powe supply
8÷36V Positive battery terminal Power supply Tensión alimentación módulo de 8 a 36V
-BAT Negative battery terminal Power supply Module supply negative
Digital Inputs
RC Fuel reserve Input NPN digital input
BPA Low oil pressure Input NPN digital input
ATA High water temperature Input NPN digital input
LT External start Input NPN digital input
PEM Emergency stop Input NPN digital input
AUX Motor auxiliary input Input NPN digital input
Pick-up/generator input
GCOM Common Input Pick-up and alternator voltage common input
PCK Pick-up Input PICK-UP input
GEN Generator Input Alternator voltage input
High voltage PNP outputs
+BAT Positive battery terminal Power supply Digital outputs supply voltage
ARR Starting Output PNP digital output of power
PR Preheating Output PNP digital output of power
PC Congurable stop Output PNP digital output of power
PNP outputs
D+ Alternator excitation Output PNP digital output
AL Alarm Output PNP digital output
CON Contactor Output PNP digital output
PD Ignition Output PNP digital output
Fig.2
M6 Control Unit Connections