DIMENSIONS, WIRING AND MECHANICAL PARTS | PAG. 15
The control unit must be mounted at the front of an electrical panel, if possible in
the centre to allow easy wiring.
There are no special ventilation requirements due to the low power consumed by
the control unit.
All outputs must be provided with the corresponding inductive current disconnec-
tion devices (diodes, varistors, RC lters, etc…).
The wiring for manoeuvres should be kept at a sufcient distance from high elec-
tric elds: at least two metres of power lines of up to 600A and 1 metre of power
lines over 600A.
5.3 CHARACTERISTICS AND INSTALLATION OF THE EQUIPMENT
EThe equipment is included within the measurement category CAT III 600V for
measurements performed in the building installation.
Disconnection means should be incorporated to the xed installation in accord-
ance with instalation regulations.
Such means must have contact separation for all poles that provide full discon-
nection in category III overvoltage conditions.
The disconnecting means, must be accessible by the user. The negative terminal
of the battery, electrical panel chassis and generator chassis must all be earthed.
After installation, the connection terminals of the Pick Up / Generator sensor in-
put (terminals GCOM, PCK, GEN) should not be accessible.
If the equipment is handled in a way not specied by the manufacturer, the equip-
ment’s protection devices could become compromised.
The surface areas of the equipment and the external face should be cleaned with
a damp cloth.
This equipment can generate the risk of danger if handled improper-
ly. It must be installed by qualied personnel. It is necessary to
consult the equipment’s documentation.
ATTENTION: risk of danger.
5.2 ELECTRICAL CHARACTERISTICS
Symbol Parameter Conditions Minimum Typical Maximum Unit
Power supply (terminals 8÷36V, –BAT, +BAT)
8÷36V Module supply voltage 8 36 VDC
+BAT Power supply of the outputs 8 36 VDC
I
BAT
Supply current 8÷36V=12V 20 60 mA
I
BAT
Supply current 8÷36V=24V 10 50 mA
P
BAT
Power consumption 1 W
NPN digital inputs (terminals RC, BPA, ATA, LT, PEM, AUX)
V
IN
Input voltage -0,7 40 V
V
IL
Low level input voltage 1 V
V
IH
High level input voltage 5 V
I
IL
Low level input current V
IN
= 0V 2 2,5 mA
I
IH
High level input current V
IN
= 24V 0 100 uA
Pick-Up / Generator input sensor (terminals GCOM, PCK, GEN)
V
IN
Pick-Up input voltage 4 30 VDC
F
IN
Pick-Up input frequency 200 2500 8000 Hz
V
IN
Generator input voltage 180 480 VAC
F
IN
Generator input frequency 45 66 Hz
Power PNP outputs (terminals ARR, PR, PC)
V
O
Output voltage +BAT V
I
O
Output current T = 1s 40 A
I
O
Output current T = 10s 20 A
I
O
Output current de salida T = ∞ 15 A
PNP outputs (terminals D+, AL, PD, CON)
V
O
Output voltage +BAT V
I
O
Output current 1 A
R
D+
Output resistance D+ 49,5 Ω
Environmental conditions and protection of the enclosure
Operating temperature -40 +85 ºC
H
R
Relative humidity
No
condensation
80 %
IP Degree of Protection *see note 1 65
Note 1: IP 65 on the front of the control unit when installed on the control panel with the sealing gasket-
provided.