PowerGem Plus User Manual
7
2 Product Specification
2.1 Size and Weight
Table 2-1 PowerGem Plus Device size
2.2 Performance Parameter
Table 2-2 PowerGem Plus performance parameter
Item
Parameter value
Rated Voltage(V)
51.2
Work Voltage Range(V)
44.8~57.6
Rated Capacity(Ah)
280
Rated Energy(kWh)
14.336
Recommend Charge/Discharge Current (A)
140
Max. continuous Charge/Discharge Current (A)
140
Peak Charge Current (A)①
160 (15s)
Peak Charge Current (A)②
180 (500ms)
Peak Discharge Current (A)③
160 (300s)
Peak Discharge Current (A)④
200(500ms)
Charge Voltage (Vdc)
56.5
①②:When it is “160Acharge current180A”the BMS will start the over-charge current
protection and cut off charge after 15s,when it is “charge current 180A”,BMS will start
protection and cut off charge after 500ms.
③④: When it is “160Acharge current200A”the BMS will start the over-discharge current
protection and cut off discharge after 300s,when it is discharge current200A”,BMS will start
protection and cut off discharge after 500ms.
Product
Nominal
Voltage
Nominal
Capacity
Weight
PowerGem Plus
DC51.2V
280Ah
113kg