© Hirschmann Rev. G 10/05/15 190166_G.DOCXG
Please refer to table below for more values.
Voltage Values displayed [mV] +/- 10mV
Pressure Transducers 300 bar, type 314
If the displayed value does differ from the actual value, please refer to the following sections to find
the cause of the problem:
If the displayed angle is incorrect, please go to section Angle Sensing.
E65
In case of an E65, the CAN-Bus converter board in the angle sensor box is reporting an internal
problem. In most cases, this will be an angle sensor, or length potentiometer. Go to those chapters
(Angle Sensing, Length Sensing) to continue trouble shooting.