Americas three-phase PDU 3P30A-8C13-3C19UL.P
The following gure and table describe the specications of the PDU.
Figure 3 Americas PDU for the Hitachi Universal V2B Rack (Three-phase PDU
3P30A-8C13-3C19UL.P)
Part
number Region Quantity
Power input
per PDU
Power
output per
PDU
Total rack
amperage
available
3P30A-8C1
3-3C19UL.P
Americas 6/rack
3/side
Three phase
208V 3P, 30A
(24A rated)
60Hz
Delta/wYe:
Delta
NEMA L15-30P
input power
plug
4.5 m (14.76
feet) cable
8 IEC C13 +
3 IEC C19
sockets
Max
allowable
current:
38.4A
8kVA
115A (24kVA)