Figure 11 APAC and EMEA PDU for the Hitachi Universal V2B Rack (Three-phase
3P30A-243-69CE-UL.P)
Part
number Region Quantity
Power input
per PDU
Power
output per
PDU
Total rack
amperage
available
3P30A-243-
69CE-UL.P
Americas,
APAC, and
EMEA
2/rack
1/side
Three phase
400/415V max.
30/32A (24A
rated) 50Hz /
60Hz
Delta/wYe: wYe
IEC309 3P + N
+ E input
power plug
4.5 m (14.76
feet) cable
24 IEC C13
+ 6 IEC C19
sockets
Max
allowable
current:
77A
17.6kVA
77A (17.6kVA)
Americas, APAC, and EMEA three-phase PDU 3P30A-243-69CE-UL.P
Appendix E: Power distribution units for Hitachi Universal V2B Rack
Hitachi Virtual Storage Platform G900 Hardware Reference Guide 119