Number Item Description
3 LAN 2 LAN port used by the user.
4 LAN 1 Maintenance LAN port used by service
personnel.
5 LAN ALARM LED Red: LAN blade can be removed.
6 Uninterruptible power supply
(UPS) port
N/A
Rack support
The storage system can be installed in the Hitachi Universal V2B rack as well as non-Hitachi
19-inch racks that meet the storage system's specifications.
For details about the Hitachi Universal V2B rack, see the Hitachi Universal V2B Rack
Reference Guide.
Non-Hitachi racks must be 4-post, EIA 310-D compliant with adequate airflow and weight
capacity. The PDUs must be mounted properly to avoid any issues for servicing the storage
system. The PDU receptacles must face toward the back (not toward each other). The area
behind the storage system and between the vertical 19-inch mounting posts must be free of
PDUs and cable loops.
Rack support
Chapter 2: Hardware overview
Hitachi Virtual Storage Platform E590 and E790 Hardware Reference Guide 21