9
X Flashing:
Changeable
Cutoff Pressure Screen
(an example)
No.0:
Capacity Control Mode
L: I-type control
No.1: Cutoff Pressure
069: 0.69 MPa
Hold down the RESET button
and press the SELECT button
more than 3 times.
Hold down the SELECT button
and press the RESET button.
No.2: Cutin Pressure
059: 0.59 MPa
No.3:
Pressure Differential
008: 0.08 MPa (unused)
No.4:
Reference Time for
Shifting to
ECOMODE
Function
030: 30 seconds
No.5: Alternative Cutoff
Pressure
069: 0.69 MPa
No.6: Alternative Cutin
Pressure
059: 0.59 MPa
SELECT
表示切替
RESET
リセット
RESET
リセット
SELECT
表示切替
RESET
リセット
SELECT
表示切替
SELECT
表示切替
RESET
リセット
Press.
Press for
each new screen.
SELECT
表示切替
Press to return.
Press.
Go to the
section (4)
Changing
the
Capacity
Control
Settings.
DigitalMonitor
5 seconds later, a
changeable decimal
place automatically
shifts.
Move to
the cutin
pressure
screen.
Press the SELECT
button to change
the cutoff pressure
setting.
3. HOW TO OPERATE [How to Use Digital Monitor and its Controls]
(3) Displaying the Capacity Control Settings
(4) Changing the Capacity Control Settings
To change the capacity control settings, do as follows:
q Display the cutoff pressure screen.
w Hold down the SELECT button and press the RESET
button. The first decimal place of the current cutoff pres-
sure setting flashes to indicate that it is changeable.
e Press the SELECT button as many times as required
until a desired number is displayed.
r Five seconds later, the first decimal place stops flash-
ing and the second decimal place flashes. Press the
SELECT button as many times as required until a
desired number is displayed.
t Press the RESET button to return to the cutoff pres-
sure screen.
y Press the SELECT button to move to the cutin pres-
sure screen. Repeat the above actions w through r
to change the cutin pressure setting. Press the RE-
SET button. The screen returns to what you have left
with the action q above.
To display the capacity control settings, do as
follows:
q Hold down the RESET button and press the
SELECT button more than 3 times. The screen
displays 0.L as an example (see the IMPOR-
TANT below).
w Press for each new screen to display the standard
and alternative cutoff and cutin pressures and the
reference time for shifting to ECOMODE control.
e Press the RESET button. The screen returns to
what you have left with the action q above.
The first screen displays the capacity control mode
symbols: A, L, or U. Each mode consists of the capac-
ity control types as follows:
A: U+I+P Type
L: U+I Type
U: U Type
The first screen also displays the that may vary
depending on the specifications.
IMPORTANT
1. Do not change the reference time for shifting to
ECOMODE control. See page 31.
2. To enable the alternative cutoff/cutin pressure func-
tion, turn on the external switch that you installed
to enable/disable this function.
IMPORTANT
Follow the section (3) Displaying the Capacity Control Settings
to display the screen where you want to change the setting.
ASpecifications
0.69MPa 0.83MPa 0.92MPa
Remark
StandardCutoffPressure
1. 069 083 092
StandardCutinPressure
2. 059 074 082
PressureDifferential
3. 008 008 008
4. 030 030 030
AlternativeCutoffPressure
5. 069 083 092
AlternativeCutinPressure
6. 059 074 082
Standard Factory Settings (in MPa without decimal point)
Unused.
Donot
change.
Available
asan
option.
ReferenceTimeforShifting
toECOMODEControl
Hitachi presets the standard cutoff pressure to the cor-
responding specification pressure. Always set the cut-
off and cutin pressures to between 050 and the speci-
fication pressure 069, 083, or 092.
IMPORTANT