No. Item Optional function
Individual
Setting
Settings Setting conditions Description
65
Fd
Upper limit of setting
temperature for heating
(Maximum value of setting
temperature allowed in
heating)
×
00
Function disabled
30 ºC is the standard maximum set
point. (factory setting)
Thisfunctiondenesthehighest
temperature setting value for
HEATING mode.
Models:
RPF(I)-)FSN2E
up to 20ºC (FC=10)
01 -1ºC(Upperlimit29ºC)
02 -2 ºC (Upper limit 28 ºC)
03 -3 ºC (Upper limit 27 ºC)
·
·
·
·
·
·
10 -10 ºC (Upper limit 20 ºC)
11 -11ºC(Upperlimit19ºC)
12 -12 ºC (Upper limit 18 ºC)
66
FE
Not used -
00
- Use at 00 conditions
01
02
67
FF
Not Used -
00
- Use as 00 conditions
01
68
H1
No indication of maintenance
alarm
×
00 Displayed This function is used to display
or hide the maintenance alarm
indication.
01 Hidden
69
H2
Indication of hot start
(No Indication of operation
limitation)
×
00 Displayed
This function is used to display
or hide the automatic control
indication.
Models:
RPF(I)-FSN2E
Not available, use at 00 conditions
01 Hidden
70
h3
Operation mode change
restriction
×
00 Unlimited operation
? NOTE
“01” is available only when one
controlleris used. Donotuse this
setting when two controllers are
used.
01
Operation mode set by central
control equipment + “Fan” mode
02
Operation mode change not
available (Hide operation mode)
(Factory setting)
71
h4
Not Used -
00
- Use as 00 conditions
01
72
H5
Not Used - 00/01 - Use as 00 conditions
73
H6
Not Used - 00/01 - Use as 00 conditions
74
J1
Not used -
00
- Use at 00 conditions
01
75
J2
Not used -
00
- Use at 00 conditions
01
76
J3
Colour of the Run indicator ×
00 Green (factory setting)
–
01 Red
77
j4
Not used - 00/01 Not used (Use as 00 conditions)
78
J5
Not used -
00
- Use at 00 conditions
01
79
J6
Not used -
00
- Use at 00 conditions
01
80
j7
Not used - 00/01 - Use as 00 conditions
OPTIONAL FUNCTION
PMML0497 rev.1 - 12/2020
17
ENGLISH