Refrigerant piping
1  Piping requirement
Model
Outerdiameterofpipe(mm)
Gas Liquid
3.0/3.5HP 15.88 9.52
4.0/5.0/6.0/6.5HP 19.05 9.52
The shorter the refrigerant piping is, the better the performance will be. So the connecting pipe should be as short as possible.
Indoor unit
Outdoor unit
PipelengthL
Height difference H
(Unit:mm)
Model
Max.pipelength
(L)
Max.height
difference(H)
Add. refrigerant 
(exceed5m)
3.0HP 30(m) 15(m) 28(g/m)
3.5/4.0/5.0/ 
6.0/6.5HP
50(m) 30(m) 28(g/m)
Refrigerant piping between indoor unit and outdoor unit
Oil trap
Slope:1/200~1/250
Slope:1/200~1/250
Oil trap
Refrigerant additional charge
Theunithasbeenlledwithrefrigerant,butifexceeds5m,additionalrefrigerant(R32)chargeisrequired.
Additionalrefrigerantcharge=(L-5)×28g/m
Oil trap
Whentheindoorunitislowerthanoutdoorunitandheightislargerthan5m,setanoiltrapevery5m(heightdifference)onsuction
piping.
NOTE:
• Toavoidstoringtoomuchoilintheoiltrap,theoiltrapshouldbeasshortaspossible.
• Thehorizontalpipingshouldbeslopedownalongtherefrigerantowdirection,tobringtheoilbacktocompressor,theslopeis
about1/200to1/250.
• Inordertoensureabettercooling/heatingperformance,therefrigerantpipingshouldbeasshortandstraightaspossible.
2  Piping material
1.  Preparelocally-suppliedcopperpipes.
2.  Selectcleancopperpipes.Makesurethatthereisnodustandmoistureinsideofthepipes.Blowtheinsideofthepipeswith
nitrogen or dry air to remove any dust or foreign materials before connecting pipes.
3. Pipingthicknessandmaterialofthepipeareshownbelow.
Unit: mm
Diameter Thickness
∅6.35 0.8
∅9.52 0.8
∅12.7 0.8
∅15.88 1.0
∅19.05 1.0
INSTALLATIONINSTRUCTIONS
HO2019292HA