2. TROUBLESHOOTING
Table 4 Drive Fault Code  (4.0/5.0/6.0/6.5HP) 
Fau
l
t 
co
de 
Fault description 
Possible reasons for abnormality 
H
ow to de
a
l
 with 
1 
Q axis c
urrent 
detection
, failure 
in 
drive 
control 
1. Compressor wire is not connected
properly;
2. Bad driver board components;
3. Compressor start load is too large;
4. Compressor demagnetization;
5. Compress or oil shortage serious
wear of crankshaft;
6. The compressor insulation fails.
1. Check compressor wire;
2. Change driver board;
3. Turn on the machine  after the
pressure is balanced again;
4. Change Compressor;
5. Change the Compressor;
6. Change the Compressor.
2 
Phase current detection, 
failure in drive control  
1.Compressor voltage default phase;
2.Bad driver board components;
3.The compressor insulation fault.
1.Check c
ompressor wire c
onnection;
2.Cha
nge th
e 
driver board;
3. Cha
nge th
e Compressor.
3 
Initialization, phase 
current imbalance
Bad driver board components.  Change driver board . 
4 
Speed estimation, 
failure in drive control 
1.Bad driver board components;
2.Compressor shaft clamping;
3.The compressor insulation fa
ils.
1.Change driver board; 
2.Change the Compressor; 
3.Change the Compressor.
5  IPM FO output fault 
1. System overload or current
overload;
2. Driver board fails;
3. Compressor oil shortage,serious
wear of crankshaft;
4. The compressor insulation fault.
1.Check the air-conditioner system;
 
2.Change the driver board;
3.Change the compressor;
4.
Change the compressor.
6 
Communication 
between driver board 
and control board fault 
1.Communication wire is not connected 
well;
2. Driver bo
ard fault;
3.
Control board fault.
1. Check compressor wire connection;
2. Change the driver board;
3. Change the control board.
7 
AC voltage,overload 
voltage 
1. Supply voltage input is too high or
too low;
2. Driver board fails.
1.Check power supply; 
2.Cha
nge the driver board.
8 
DC voltage,overload 
voltage 
1. Supply voltage input is too high ;
2. Driver board fault.
1. Check power supply;
2. Change the driver board;
9  AC voltage imbalance 
Driver board fails.  Change the driver board. 
10 
The PFC current 
detection circuit fault 
before compressor is 
ON 
Bad driver boa
rd components 
Change the driver board. 
11 
AC voltage supply in 
outrange 
1.Power supply abnormal, power
frequency out of range; 
2.Driver board fails.
1. Check the system;
2. Change the driver board.
12 
Products of 
single-phase PFC 
over-current, FO 
output low level 
1.System overload, current is too large;
2. Driver board fault;
3. PFC fault.
1. Check the system;
2. Change the driver board;
3. Change PFC.
Inverter over current 
(3-phase power supply 
air conditioners) 
1. System overload, current is too large;
2. Driver board fault;
3. Compressor oil shortage, serious
wear of crankshaft;
4. The compressor insulation fault.
1. Check the s
y
stem;
2.
Cha
nge th
e 
driver board;
3. Change the compressor;
4. Change the compressor.
13  Inverter over current 
1. System overload, current is too large;
2. Driver board fault;
3. Compressor oil shortage,serious
wear of crankshaft;
4. The compressor insulation fault.
1. Check the system;
2. Change the driver board;
3. Change the compressor;
4. Change the compressor.
14 
PFC over 
current(single-phase 
air-conditioner) 
1. System overload, current is too large;
2. Driver board fault;
3. PFC fault.
1. Check the system;
2. Change the driver board;
3. Change PFC.
Phase imbalance or 
phase lacks or the 
instantaneous power 
failure (only for 
3-phase power supply
air conditioners)
1.3-Phase voltage imbalance; 
2.The 3-phase power s
upply phase
is lost;
3. Power supply wiring is wrong;
4. Driver bo
ard fault.
1, Check the power supply; 
2. Check the power supply;
3. Check the power supply wiring
connection;
4.Change the driver board.
15 
The instantaneous 
power off detection 
1.The power supply is not stable ;
2.The instantaneous power failure ;
3.Driver board fault;
1. Check the power supply;
2. Not fault;
3. Change the driver board.