5. CONTORL LOGIC DESCRIPTION
5. Control logic description
5.1 Fan only mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no set temperature is displayed.
(3) Indoor fan can be set to high/medium/low, but can not be set to auto.
5.2 Cooling mode
Indoor fan running rules:
In cooling mode, indoor fan runs all the time and the speed can be selected as high,
(medium), low and auto.
The auto fan:
T1 is indoor room temperature. Ts is set temperature.
Inverter outdoor unit
Compressor and outdoor fan running rules:
Once the compressor starts up, it will follow the below rules:
When indoor room temp.T1 is lower than Ts, the compressor and outdoor fan will shut off.
When T1 is higher than Ts+1, the compressor and outdoor fan will start up.
Outdoor fan running rules:
Once the outdoor fan starts up, it will follow the below rules:
Single outdoor fan: First, it will run in an invariable speed for a short time; Then it will regulate
the speed by the outdoor-coil temperature.
Double outdoor fan: If it has two outdoor fans, the upper fan regulates the speed by the
rules, and the downer fan speed lower than the upper fan speed for 30rpm~60rpm.
T
1-
Ts
0
2
4
Low
Medium
High
Ts-1
46