1. How to count the lamp blinking frequency
・The product will repeat blinking with 2-second
intermissions.
・The blinking speed is as follows: on for 0.35 seconds and
off for 0.35 seconds.
While the "timer lamp" (orange), the "clean lamp" (yellow), the "mist and air purification lamp" (yellow) or "monitor
lamp" (yellow) of the indoor unit is blinking, troubleshoot the product while referring to the table below.
2. If you wish to try another operation while the lamp is blinking, operate the START/STOP button on the remote control unit
twice. The first push will reset the indoor microcomputer, while the second will activate the product
(except for the mode in ※1).
[Cautions]
・There is a failure mode displayed only while the self-diagnosis memory is read (※2). Read and check it as necessary.
・ An erroneous connection (a wrong insertion) of terminals A or B of F cable may go undetected.
Self-diagnosis display function (indoor side display)
[An example of 5-time blinking]
2-second
intermission
2-second
intermission
REFER TO THE TABLE BELOW IF THE TIMER INDICATOR
(
ORANGE
)
IS BLINKING.
・FAILURE OF THE PELTIER DEVICE
・FAILURE OF THE POWER SUPPLY
CIRCUIT OF PELTIER DEVICE
・FAILURE OF THE HIGH VOLTAGE
GENERATOR OR ELECTRODE
REFER TO THE TABLE BELOW IF THE MONITOR INDICATOR
(YELLOW) IS BLINKING.
※IF THE INTERFACE CIRCUIT IS DEFECTIVE WHEN
THE POWER IS TURNED ON
,
THE SELF-DIAGNOSIS
INDICATION WILL NOT WORK.
LIGHTS FOR 0.35 SEC. AT
INTERVAL OF 0.35SEC.
SWITCH P. W.B. DEFECTIVE
・FAILURE OF THE CLEANING UNIT
DRIVING MOTOR
・FAILURE OF THE CLEANING UNIT
POSITION DETECTION SWITCH
・THE FRONT PANEL IS OPEN DURING
CLEANING UNIT OPERATION, DURING
ELECTRIC DUST COLLECTOR OPERATION
OR DURING ION MIST OPERATION
PEAK CURRENT CUT
ABNORMAL LOW SPEED ROTATI ON
SWITCHING FAILURE
OH THERMISTOR TEMP.RISE
THERMISTOR ABNORMAL
COMMUNICATION ERROR
ABNORMAL POWER SOURCE
FAN LOCK ERROR
EEPROM READ ERROR
HIGH VOLTAGE GENERATOR DEFECTIVE
OVERLOAD LOWER LIMIT CUT
FAN STOP FOR STRONG WIND
OF DC FAN MOTOR
2 TIMES
3 TIMES
5 TIMES
9 TIMES
10 TIMES
12 TIMES
11 TIMES
13 TIMES
FAILURE OF THE PELTIER DEVICE
LIGHT DOWN MODE: LIGHTING / DECREASING LIGHTS / OFF
CONNECTING CORD DEFECTIVE
OUTDOOR DEFECTIVE
CLEANING UNIT DEFECTIVE
11 TIMES
19 TIMES
POWER RELAY DEFECTIVE
LAMP BLINKING MODE
MAIN DEFECTIVE
LIGHTING:4SEC.
OFF:1SEC.
LIGHTING:1SEC.
DECREASING
LIGHT:1SEC.
LAMP BLINKING MODE MAIN DEFECTIVE
LIGHTING:4SEC.
OFF :3SEC.
LAMP BLINKING MODE MAIN DEFECTIVE
LAMP BLINKING MODE MAIN DEFECTIVE
DESCRIPTION OF THE SELF-DIAGNOSIS INDICATION
REVERSING VALVE DEFECTIVE
ABNORMAL ROTATI NG NUMBERS
ONCE
FORCED OPERATION OF OUTDOOR UNIT
INDOOR/OUTDOOR INTERFACE DEFECTIVE
LAMP BLINKING MODE MAIN DEFECTIVE
INDOORTHERMISTOR DEFECTIVE
IC401 DEFECTIVE
17 TIMES
18 TIMES
LIGHTING:4SEC.
OFF :1SEC.
COME OFF OR DISCONNECTION OF
THECONNECTOR CN17
※IF THE INDOOR UNIT CAN NOT BE OPERATED AT ALL
,
CHECK THE CONNECTION OF THE CONNECTING CORD.
(
REVERSE CONNECTION OR DISCONNECTION
)
REFER TO THE TABLE BELOW IF THE INDOOR UNIT
DOSE NOT WORK AT ALL.
10 TIMES
9 TIMES
2 TIMES
3 TIMES
4 TIMES
5 TIMES
6 TIMES
7 TIMES
12 TIMES
13 TIMES
FU1 3A-FUSE BLOWN
REFER TO THE SERVICE GUIDE FOR
HOW TO DETERMINE THE FAILED PA RT
CHECK POINT
ACTION/REPLACEMENT PA RTS
,
etc
FIX CN16 CONNECTOR
COME OFF OR DISCONNECTION
OF THE CONNECTOR FOR
INDICATING P.W.B.
REPLACE THE PA RT WHICH CAUSED BLOWING/
DISCONNECTION OF 3A-FUSE
FAILURE OF CONTROL P.W.B.
THE BLINKING OTHER THAN MENTIONED ABOVE ARE OUTDOOR'S
SELF-DIAGNOSIS INDICATION.
REFER TO OUTDOOR'S LAMP-LABEL FOR DETAILS.
LIGHTING:4SEC
OFF :1SEC.
REFER TO THE TABLE BELOW IF MIST・AIR PURIFY
INDICATOR(YELLOW) IS BLINKING.
REFER TO THE TABLE BELOW IF THE CLEAN INDICATOR
(
YELLOW
)
IS BLINKING.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
2sec.
※2
※1
※2
※2
– 112 –
※2
※2
※2
※2