6. Optional functions
162
SMGB0079 rev.0 - 01/2013
Items Optional function
Individual
setting
Setting
condition
Contents
C2 Not prepared - “- -” Fixed Not used
C3 Not prepared -
00 Not used
01 (Use as 00 conditions)
C4 Not prepared -
00 Not used
01 (Use as 00 conditions)
C5
Static pressure selection (RPI)
00 Average static pressure (factory set)
01 High static pressure
02 Low static pressure
Increased fan speed (RCI, RCIM, RCD)
00 Normal
01 Speed increase 1
02 Speed increase 2
C6 Increasing fan speed
00 Not available
01 Available
C7 Canceling 3 minutes compressor guard
00 Standard
01 Cancellation
C8 Thermistor of remote control switch
00 Control by indoor suction thermistor
01 Control by thermistor of remote control switch
02
Control by average value of indoor suction
thermistor and thermistor of remote control switch
C9 Not prepared - “- -” Fixed Not used
CA Not prepared - “- -” Fixed Not used
Cb Selection of forced stoppage logic ×
00 Forced stoppage input: A contact
01 Forced stoppage input: B contact
CC Not prepared ×
00 Not used
01 (Use as 00 conditions)
Cd Not prepared
00 Not used
01 (Use as 00 conditions)
CE Not prepared -
00 Not used
01 (Use as 00 conditions)
CF Change of louver swing angle
00 Standard (7 steps)
01 Draft prevention (5 steps)
02 High ceiling (5 steps) (*2)
d1 Power supply ON/OFF 1
00 Not available
01 Available
d2 Not prepared - “- -” Fixed Not used
d3 Power Supply ON/OFF 2
00 Not available
01 Available
d4
Prevention for cooling discharge air tempera-
ture decrease
00 Not available
01 Available
d5
Prevention for heating discharge air tempera-
ture decrease
00 Not available
01 Available
d6 Room temperature control for energy saving
00 Not available
01 Available
d7 Not prepared 00~07
Not used
(Use as 00 conditions)