8. Troubleshooting
249
SMGB0079 rev.0 - 01/2013
8
Alarm code
57
Abnormality of fan motor protection (DC fan motor) for RAS-(4-6)H(V)NCE
• The RUN LED ickers and “ALARM” is displayed on the remote control switch.
• The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
- This alarm is indicated when the revolution pulse output from the fan motor is 10 rpm or less and the
reverse revolution signal is detected. The fan motor is stopped once, and restarted after 10 seconds.
If it occurs more than 10 times in 5 minutes after the rst abnormality occurs, this alarm is indicated. The abnormality
occurs when the fan motor is stopped by slugging.