2. Unit Installation
36
SMGB0079 rev.0 - 01/2013
Wind guard
Specications
Model WSP-335A
Quantity 1per unit
1
1
2
2
3
1 Mounting dimension
2 Air ow
3 3 4xØ7
Material
Galvanized sheet metal +
baked painting
Color Gray (1.0Y8.5/0.5)
Weight 5.5 kg
Accessories
Fixing screw
x 4 [M5 (SUS) x 12]
Installation manual
Installation
restriction
“Guard net” “Air ow guide” or “Snow protection
hood” is not available to install with Wind guard
Attaching example of air wind guard
Attach the air ow guide to the air discharge grille with four (4) screws (supplied).
The xing holes are located at 4 positions on the grille. (Screw tightening torque 2.4 3.1 N.m)
Do not remove the air discharge grille for air ow guide installation.
C A U T I O N
Iftheairguideisinstalledwithoutdischargegrilleitmaycauseinjuryduetorotatingfan.
One windguard cover installation
1 Air discharge grille
2 Wind guard
3 Air discharge grille
4 Outdoor unit
5 M5 xing screw x4 (Accessories)
1
2
3
4
5
Service space
Both sides of the outdoor unit should be open.
No obstacles should be placed in the air discharge side.
1 Min. 200 mm
2 Outdoor unit
3 Wind guard
1
2
3

Table of Contents