10 Servicing
408
SMGB0064 rev.0 - 08/2011
4 Removing Electrical Components.
Remove the xing screw and remove the reactor.
• To mount components be sure to match the wiring connection with the mark band codes.
1
2
3
4
5
6
1. Electrical box cover.
2. Partition plate.
3. Fuse.
4. Electrical box.
5. Reactor.
6. See the note.
N O T E
• The PCB cannot be removed from the electrical box. To replace PCB the entire electrical box must be replaced.
• DO NOT touch electrical components while the LED1 (Red) is ON to avoid electrical shock. Wait until the LED
turns off.
10.3.2 Outdoor Units RAS-(4-6)H(V)RNS2E
Removing service cover
N O T E
Follow the procedure below to remove main parts and components. For mounting follow the reverse procedure
of removal.
Do not expose the refrigerant cycle to the atmosphere for a long period to avoid moisture or dust entering into
the cycle. Be sure to replace parts immediately after removing. Seal the refrigerant cycle when left unattached for
a long period.