7. Test run
174
SMGB0079 rev.0 - 01/2013
9 
To finish the test run, press “
” (run/stop)  again or pass 
over the set test run time. When changing the test run time, 
press “
” or “ ” to select “T-RUN TIME”. Then, set the test 
run time (30 to 600 minutes) by pressing “
” or “ ”
Test Run: 2 units
MODE
SPEED
MED
COOL
LOUV.
SEL. ADJ
T-RUN TIME
510MIN
STOP
 -
The RUN indicator on the remote control switch ashes 
when some  abnormalities such  as protection devices 
activated occur during the test run as well as the RUN 
indicator (orange) on the indoor unit ashes (0.5 second 
ON/ 0.5  second OFF).   Additionally, the alarm  code, 
the unit model code and connected number of indoor 
units  will  be  displayed  on  the  LCD  as shown  in the 
figure below.  If the RUN indicator on PC-ARF flashes 
(2 seconds ON/ 2 seconds OFF), it may be a failure in 
the transmission between the indoor unit and the remote 
control switch  (loosening  of connector, disconnecting 
wiring or breaking wire, etc.).  In this case, check the 
item 8.3 “Alarm Code” and perform for troubleshooting.  
Consult to authorized service engineers if abnormality 
can not be recovered.
SEL. OP MODE
MODEL : b .02
Alarm Code: 
22
01-02
ALM RST
ADDR
ENT.
OK