23
INSTALLATION AND OPERATION MANUAL
ENGLISH
9 REFRIGERANT CYCLE
EXAMPLE:
No. Part Name No. Part Name
1 Compressor 14 Ambient Thermistor
2 Outdoor Heat Exchanger 15 Evaporating Pipe Thermistor
3 Accumulator 16 Gas Discharge Thermistor
4 Expansion valve 17 Capillary Tube
5 Reversing Valve 18 Strainer
6 Solenoid Valve 19 Branch Pipe (liquid)
7 Strainer 20 Branch Pipe (gas)
8 Distributor 21 Indoor Heat Exchanger
9 Check Joint 22 Strainer
10 High Pressure Switch Protection 23 Expansion valve
11 Sensor for Refrigerant Protection 24 Distributor
12 Stop Valve for Gas Line
25 Silencer
13 Stop Valve for Liquid Line
10 UNITS INSTALLATION
10.1. OUTDOOR UNITS INSTALLATION
CAUTION:
Transport the products as close to the installation location as
practical before unpacking.
Do not put any material on the products.
Apply four lifting wires on to the outdoor, when lifting it by crane
WARNING:
- Install the outdoor unit with sufcient clearance around it for
operation and maintenance as shown in the next gures.
Install the outdoor unit where good ventilation is available
- Do not install the outdoor unit where is a high level of oil mist,
salty air or sulphurous atmosphere.
- Install the outdoor unit as far as practical (being at least 3 meters)
from electromagnetic wave radiator (such as medical equipment).
- For cleaning, use noninammable and nontoxic cleaning liquid.
Use of inammable agent may cause explosion or re.
- Work with sufcient ventilation, for working in an enclosed space
may cause oxygen deciency. Toxic gas may be produced when
cleaning agent is heated to high temperature by, e.g., being
exposed to re.
- Cleaning liquid shall be collected after cleaning.
- Pay attention not to clamp cables when attaching the service
cover to avoid electric shock or re.
CAUTION:
Keep clearance between the units of more than 50mm, and avoid
obstacles that may hamper air intake, when installing more than
one units together.
Install the outdoor unit in the shade or not exposed to direct
sunshine or direct radiation from high temperature heat source.
Do not install the Outdoor Unit in a space where a seasonal wind
directly blows to the Outdoor fan.
Check to ensure that the foundation is at, level and sufciently
strong.
Install the unit in a restricted area not accessible by the general
public
Aluminum ns have very sharp edges. Pay attention to the ns to
avoid injury.
R410A 4.15 MPa
Refrigerant Flow
for Cooling
Refrigerant Flow
for Heating
Field Refrigerant
Piping
Flare Connection Flange Connection Brazing Connection Refrigerant:
Airtight Test
Pressure:
PMML0197_r0_04-10.indb 23 08/07/2010 9:20:30