INSTALLATION AND OPERATION MANUAL
15.1. TEST RUN PROCEDURE BY REMOTE CONTROL SWITCH
Turn ON the power source of the Indoor and Outdoor Units
Set the TEST RUN mode by remote control switch.
Depress the “MODE” and the “ OK” switches simultaneously for more than 3
seconds.
a) If “TEST RUN” and the counting number of the connected units to the remote
control switch (for example “”) are indicated on the remote control switch,
the connection of remote control cable is correct.→Go to
b) If no indication appear or the number of the units indicated is smaller than the
actual number of the units, some abnormalities exist.→Go to
Remote Control Switch
Indication
Wrong Portions Inspection Points after Power Source OFF
No indication
- The power source of Outdoor Unit is not turned
ON.
- The connection of the remote control cable is
incorrect.
1. Connecting Points of Remote Control Cable terminal board of Remote Control switch and
indoor unit.
2. Contact of Terminals of Remote Control Cable
- The connecting wires of power supply line are
incorrect or loosened.
3. Connection Order of each Terminal Board
4. Screw Fastening of each Terminal Boards.
Counting number of
connected units is incorrect
- The power source of Outdoor Unit is not turned
ON.
- The operating line wiring between indoor unit
and outdoor unit is not connected.
- The connection of control cables between each
indoor units are incorrect. (When one remote
control switch controls multiple units)
5. Dip Switch Setting on Printed Circuit Board
6. Connecting on the PCB
7. This is the same as item 1, 2 , and 3.
Back to after checking
Select TEST RUNNING MODE by depressing MODE Switch (COOL OR HEAT)
Depress RUN/STOP switch.
a The TEST RUN operation will be started. (The 2 hours OFF-TIMER will be set and the TEST RUN operation will be nished after 2 hours unit operation or by depressing the
RUN/STOP switch again).
NOTE:
TEST RUN operation ignores the temperature limitation and ambient temperature during heating operation to have a continuous operation, but the protections are alive.
Therefore, the protection may activate when the heating TEST RUN operation is performed in high ambient temperature.
TEST RUN operation time can be modifyed / increased depressing the time switch in the Remote Control.
b If the unit do not start or the operation lamp on the remote control switch is ickered, some abnormalities exist. →Go to
Remote Control
Switch Indication
Unit Condition Wrong Portions Inspection Points after Power Source OFF
The operation lamp ickers.
(1 time/1 sec.) And the Unit
No. and Alarm Code “03”
icker
The unit does not start.
The power source of Outdoor Unit in not
turned ON.
The connecting wires of operating line
are incorrect or loosened.
1. Connecting Order of each Terminal Board.
2. Screw fastening of each Terminal Boards.
NOTE:
Recovering method of FUSE for operating
circuit. There is a fuse (FUSE4 on Indoor Unit
PCB1, EF1 on Outdoor Unit PCB1) to protect
operating circuit on the PCB, when the power
lines are connected to operating lines. If fuse
is melted, operating circuit can be recovered
once by setting the dip switch on the PCB as
shown in
The operation lamp ickers.
(1 time/2 sec.)
The unit does not start.
Remote control cable is broken.
Contact of connectors is not good.
The connection of remote control cable
is incorrect
This is the same as item 1 and 2
Indication of Flicker except
above
The unit does not start, or start once and then
stops
The connection of thermistor or other
connectors are incorrect. Tripping of
protector exists, or else.
Check by the abnormality mode table in the
Technical Catalogue (Do it by service people).
The operation lamp Flickers.
(1 Time/1s)
Unit No. , Alarm Code 
and Unit Code E icker
The unit does not start.
The connection of the remote control
cable between Indoor Units is incorrect.
Check by the abnormality mode table in the
Technical Catalog (Do it by service people).
Back to after checking
Instructions fot the recovery when the fuse of the transmission circuit is blown out:
1. Correct the wiring to the terminal board.
2. Set the 1st pin of DSW7 on the indoor unit PCB to ON
Set the DSW7 on the indoor unit PCB to ON
(Only RPK-1.0/1.5)
Except RPK 1.0/1.5 Only RPK-1.0/1.5
Counting
number of
connected
units

Operation lamp
PMML0197_r0_04-10.indb 38 08/07/2010 9:20:59