Piping direction
Fix the pipes adequately in order to avoid vibration and excessive 
force to the valve.
1  The pipes can be installed in three directions (front, rear or 
bottom side) from the bottom base. For vibration protection, 
properly x the piping connection and check that no exces-
sive force is applied to the stop valve.
Front side
Rear side
Bottom side
Bottom base
2  Operation of the stop valve should be performed according 
the specied in this manunal.
3  Connect the pipes according to the tables.
4  Completely  seal  the  penetration  part  at  the  bottom  of  the 
pipes with insulation in order to prevent rain water from enter-
ing the conduit.
For heat pump systems (2 pipes)
For piping from bottom base
For piping from front or  
rear side piping cover
Piping cover  
(attached to unit)
Gas pipe
Liquid pipe
Cover the gap 
with insulations
Gas pipe
Liquid pipe
Piping 
cover
Cover the gap with a 
packing (eld-supplied)
For heat recovery systems (3 pipes)
For piping from bottom base
For piping from front or  
rear side piping cover
Piping cover  
(attached  
to unit)
Gas pipe
Liquid pipe
Cover the gap  
with insulations
Gas pipe
Liquid pipe
Piping 
cover
Cover the gap with a 
packing (eld-supplied)
Heat recovery systems (3 pipes)
Refrigerant gas piping 
connection  
(Low pressure)
Refrigerant gas piping connection  
(High/Low pressure)
Refrigerant liquid piping connection
Refrigerant piping and  
wiring connection holes  
(knockout holes)
Refrigerant gas piping connection  
(High/Low pressure)
Refrigerant liquid piping connection
Refrigerant gas piping connection  
(High/Low pressure)
Refrigerant gas piping connection  
(High/Low pressure)
Square holes at  
front and back sides
Refrigerant liquid piping connection
Refrigerant gas piping connection  
(High/Low pressure)
85
82 250
130 108
132
110
19065
289
275
2 Control cable outlets  
(∅33 knockout hole)
Power source cable outlet 
(∅65 knockout hole)
Refrigerant piping outlet 
(high/low pressure gas, liquid) 
(knockout square hole)
Refrigerant piping outlet 
(Low pressure gas)
(mm)
Model A B C D E F G
RAS-8FSXN1E
∅19.05 ∅15.88 ∅9.52
150 150 340 205
RAS-10FSXN1E
∅22.2 ∅19.05 ∅9.52
RAS-12FSXN1E
∅25.4 ∅22.20 ∅12.70
170 170 325 200RAS-14FSXN1E
∅25.4 ∅22.20 ∅12.70
RAS-16FSXN1E
∅28.58 ∅22.20 ∅12.70
(mm)
Model A B C D E F G
RAS-5FSXNH(E)
∅15.88 ∅12.70 ∅9.52
150 150
340 205
RAS-6FSXNH(E)
∅19.05 ∅15.88 ∅9.52
RAS-8FSXNH(E)
∅19.05 ∅15.88 ∅9.52
170 170RAS-10FSXNH(E)
∅22.2 ∅19.05 ∅9.52
RAS-12FSXNH(E)
∅25.4 ∅22.20 ∅12.70
33
PMML0294A rev.2 - 07/2014
Piping work and refrigerant charge