Insulation work
1  Securely  insulate  high/low  pressure  and  low  pressure  (for 
heat recovery system only) gas piping side and liquid piping 
side individually. Make sure to insulate the union are nut for 
the piping connection as well.
2  Mount the piping cover equipped with the outdoor unit after 
connecting the pipe. Completely seal the penetration part at 
the bottom of the pipes with insulation in order to prevent rain 
water from entering the conduit.
3  Cover  the  gap  between  the  piping  cover  and  pipes  with  a 
packing (eld-supplied) after the insulation work is completed.
  NOTE
If the gap is not covered, the unit may be damaged if snow, rain 
water or animals enter the unit.
For piping from botton base
For piping from front or  
rear side piping cover
Piping cover  
(attached to unit)
Gas pipe
Liquid pipe
Cover the gap 
with insulations
Gas pipe
Liquid pipe
Piping 
cover
Cover the gap with a 
packing (eld-supplied)
9.2  VACUUMING
1  Connect  a manifold gauge and vacuum pump  to  the check 
joints*.
Heat pump system
High/low pressure gas stop valve 
Liquid stop valve
Heat recovery system
High/low pressure gas stop valve
Low pressure gas stop valve
Liquid stop valve
2  Continue  vacuum  pumping work until the pressure reaches 
-0.1MPa  (-756mmHg)  or  lower  for  one  to  two  hours.  After 
vacuum pumping work, stop the vacuum pumping and leave 
the gauge for one hour.  Check to ensure that the pressure in 
the manifold gauge does not increase.
3  Tighten  the  caps  of  check  joint  according  to  the  specied 
torque (Item 8.1-(2)-(e)) after the vacuum pumping work.
4  If  the  pressure  inside  the  gauge  does  not  reach  -0.1MPa 
(-756mmHg),  it  is  considered  that  there  is  a  gas  leakage. 
Check for any gas leakage once again. If no leakage exists, 
operate the vacuum pumping for one to two hours. If moisture 
remains inside the pipes, the compressor may be damaged.
  NOTE
•  If tools or measuring instruments come into contact with the 
refrigerant, use the tools or the measuring instruments exclu-
sively for R410A.
•  DO NOT perform vacuuming pumping work with valves of the 
outdoor units open. Otherwise, the refrigerant charged before 
shipment may leak and it may result in failure.
50
PMML0294A rev.2 - 07/2014
Additional refrigerant charge
PMML0294A_rev.2_02-2014.indb   50 14/07/2014   12:28:30